期刊文献+

重庆地区地埋管地源热泵系统的某工程应用分析 被引量:3

An Engineering Application Analysis of Ground Source Heat Pump in Chongqing
下载PDF
导出
摘要 对重庆地区某办公楼的地埋管地源热泵系统进行了经济性和节能性分析,其中节能性分析是依据测试结果进行的。经济性分析结果表明:本工程采用地埋管地源热泵系统,相比空气源热泵系统,初投资静态回收期为12年;相比冷水机组+燃气锅炉,初投资静态回收期为14.1年。节能性分析结果表明:本工程采用地埋管地源热泵系统,系统制冷和制热能效比分别能达到3.6和2.9;夏季,相比于空气源热泵,系统能效提高率为20.0%,相比于冷水机组,系统能效提高率为2.9%;冬季,相比于空气源热泵,系统能效提高率为16.0%,相比于燃气锅炉,系统能效提高率为26.7%。 This paper analysis the economic and energy efficiency of the ground source heat pump system of an office building in Chongqing, in which the energy efficiency analysis is based on the test results. Economic analysis shows that: compared to the air-source heat pump system, the static payback period of the initial investment is 12 years; compared to the water chiller + gas boiler system, the static payback period of the initial investment is 14.1 years. Energy efficiency analysis shows that: the cooling and heating energy efficiency of the ground source heat pump system can reach 3.6 and 2.9 respectively; in summer, the system efficiency is increased by 20.0% compared to the air-source heat pump system and 2.9% compared to the water chiller; in winter, the system efficiency is increased by 16.0% compared to the air-source heat pump system and 26.7% compared to the gas boiler.
机构地区 重庆大学
出处 《制冷与空调(四川)》 2013年第6期588-592,共5页 Refrigeration and Air Conditioning
关键词 地埋管地源热泵系统 经济性 节能性 静态回收期 系统能效 ground source heat pump system economic energy efficiency the static payback period system efficiency
  • 相关文献

参考文献5

二级参考文献48

共引文献35

同被引文献19

引证文献3

二级引证文献5

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部