期刊文献+

典型通信机房设备发热量测试分析 被引量:2

The test and analysis of device heat dissipation in typical telecommunication equipment room
下载PDF
导出
摘要 对西安某通信机房进行设备发热量测试,得到机房内设备发热量参数.引用通信机房空调系统设计时常用的发热量估算方法对该通信机房的设备发热量进行估算,得出的结果与实测值及理论值进行对比,找出二者间的关系.根据对比的结果可以发现,针对现有通信机房,可以使用实测的方法对空调系统负荷进行核算. The device heat dissipation data of a telecommunication equipment room in Xi'an was meas- ured. Meanwhile the device heat dissipation data was estimated by using the related method. Their rela- tionship was found out by comparing and analyzing the measured data and theoretical data. According to the results of the comparison,the method of actually measured could be used to check the air condition load of other telecommunication equipment room.
出处 《西安工程大学学报》 CAS 2013年第6期773-778,共6页 Journal of Xi’an Polytechnic University
基金 陕西省科技统筹创新工程计划项目(2011KTCQ01-10)
关键词 通信机房 设备发热量 发热量测试 机房空调 冷负荷 telecommunication equipment room:device heat dissipation the method of device heat dissi-pation air conditioning of telecommunication equipment room cooling load