某制药车间二次泵系统节能改造分析

Energy-Saving Rebuilding Analysis of Secondary Pump System in a Pharmaceutical Plant
下载PDF
导出
摘要 介绍上海生物制品研究所有限责任公司某车间冷冻水二次泵系统,对该系统进行了详细的功率、流量、压力测试,发现该二次泵系统存在旁通流量大,水泵控制方式落后等问题,并针对这些问题进行了二次泵系统的节能改造。经过测试,改造的节能效果显著,对类似实际工程有较好的借鉴意义。 This paper first gives a brief introduction of secondary chilled water pump system of a workshop in Shanghai Institute of biological products. Then a detailed test of the system, including power, flow rate, pressure showed some problems, such as serious bypass, outdated control method. Finally, some corresponding rebuilding was carried out, and showed significant energy-saving effect. This study has a good meaningful reference on practical engineering.
出处 《上海节能》 2013年第12期38-41,共4页 Shanghai Energy Saving
关键词 净化空调 二次泵系统 一次泵 变频 旁通阀 clean air-conditioning secondary pump system primary pump frequency con-version bypass-valve