期刊文献+

三相PWM变流器谐波阻抗的研究 被引量:2

Research on the Harmonic Impedance of Three-phase PWM Converter
下载PDF
导出
摘要 变流器的谐波阻抗是系统稳定性分析、滤波器优化设计中的重要参数。以典型的三相PWM逆变器为例,研究了三相PWM逆变器在abc坐标系下与dq坐标系下的输出阻抗模型,并采用谐波电流注入法,对逆变器的输出阻抗进行测量,从而得到三相P W M变流器的谐波阻抗参数。采用仿真实验对理论分析进行了验证。 Harmonic impedance is a key parameter used to analyze the stability of system, optimized design of filter, and so developed an output impedance model in abc coordinates and dq coordinates as an example of a typical three-phase PWM inverter. Output impedance of the inverter was extracted and measured by injecting a current perturbation and the parameter of harmonic impedance was got. Simulation results validate the theoretical analysis.
出处 《大功率变流技术》 2013年第6期52-55,共4页 HIGH POWER CONVERTER TECHNOLOGY
基金 国家自然科学基金(51177130) 台达2011电力电子科教发展计划重点项目(DREK2011002)
关键词 三相PWM变流器 谐波阻抗 阻抗测量 three-phase PWM converter harmonic impedance current injection
  • 相关文献

参考文献4

二级参考文献59

共引文献119

同被引文献18

  • 1SHI H T,ZHUO F,HOU L X,et al. Small-signal Stability Analysis of A Microgrid Operating in Droop Control Mode[C]. Melbourne,2013 IEEE Energy Conversion Congress and Exposition Asia, 2013.
  • 2GUERRERO J M,VICUNA L G,MATAS J,et al. Output Impedance Design of Parallel-connected UPS Inverters with Wireless Iad-sharing Control[J]. IEEE Transactions on Indusal Electronics,2005,52(4) : 1126-1135.
  • 3SHI H T,UANG Z,YRE X L,et al.Calculation and Measurement of Harmonic Impedance for A Microgrid Operating in Islanding Mode[C]. Harbin:2012 IEEE 7th Interna-tional Power Electronics and Motion Control Conference-ECCE Asia,2012.
  • 4XIAO Y,MAUN J C,MAHMOUD H B,et al.Harmonic Impedance Measurement Using Voltage and Current Increments from Disturbing Loads[C].Rome:9th International Power Conference on Harmonics and Quality of Power,2000.
  • 5YANG Z,HONG T S,XIAO L Y,et al.Harmonic Impedance Measurement for An Islanded Microgrid Using Current Injection[C].Harbin:Seventh International Conference on Power Electronics and Motion Control,2012,1:373-378.
  • 6SHI H T,YANG Z,YUE X L,et al.Calculation and Measurement of Harmonic Impedance for A Microgrid Operating in Islanding Mode[C].Harbin:Seventh International Conference on Power Electronics and Motion Control,2012,1:356-361.
  • 7HOU L X,SHI H T,YANG Z,et al.Harmonic Impedance Calculation and Measurement for An Islanded Microgrid[C].Melbourne:ECCE Asia,2013:550-554.
  • 8BELKHAYAT M,WILLIAMS M L.Impedance Extraction Techniques for DC and AC Systems[C].Philadelphia:Naval Symp.Electric Mach.,2000.
  • 9HUANG J,CORZINE K A,BELKHAYAT M.Small-signal Impedance Measurement of Power-electronics-based AC Power Systems Using Line-to-line Current Injection[J].IEEE Transactions on Power Electronics,2009,24 (2):445-455.
  • 10HUI J,FREITAS W,VIEIRA J C M,et al.Utility Harmonic Impedance Measurement Based on Data Selection[J].IEEE Transactions on Power Delivery,2012,27 (4):2193-2202.