忽视电磁铁剩磁对铁芯动作的影响,以及对电磁铁内的垫片、结构任意改变,将导致断路器机构不能正常动作。本文对一起因分闸电磁铁剩磁导致断路器不能正常动作的原因进行检查分析,并提出预防措施。
This paper ignored the influence of electromagnet residual magnetism to iron core operation. The change of spacer in electromagnet and its construction caused the breaker could not normally act. This paper analyzed the reason why the breaker could not normally act caused by tripping electromagnet residual magnetism, and proposed the precautionary measures.
出处
《贵州电力技术》
2014年第2期32-33,共2页
Guizhou Electric Power Technology
关键词
断路器
CT10机构
不能合闸
剩磁
垫片
间隙
breaker
CT10 organization
failed to switch on
residual magnetism
spacer