期刊文献+

外遮阳对室内热环境影响分析 被引量:1

Evaluation of the Influence on Indoor Thermal Performance Caused by Exterior Shading Device
下载PDF
导出
摘要 本文对两间玻璃实验房进行了测试,采用Gennusa平均辐射温度(Tr*)模型,从室内操作温度、辐射温度不对称度以及PMV-PPD三个方面,研究了遮阳对室内热环境的影响。采用Tr*评价后结果显示,使用外遮阳后,测点辐射不对称度最高从25℃降至5℃以内,PMV最高从2降至-0.2,室内热环境得到显著改善。 In this paper, a comparative field measurement was done in two test rooms. After that, the influence of exterior shading device on indoor thermal performance is evaluated from different aspects namely operative temperature, radiant temperature asymmetry and PMV-PPD. Using Gennusa's model of mean radiant temperature, radiant temperature asymmetry drops from 25℃ to 5℃ and PMV drops from 2 to -0.2 after blind was on, which proves that exterior shading device has a significant effect on indoor thermal environment.
出处 《建筑热能通风空调》 2013年第5期38-41,33,共5页 Building Energy & Environment
基金 国家自然科学基金青年科学基金项目(51208363)
关键词 外遮阳 热环境 平均辐射温度 太阳辐射 exterior shading device, thermal environment, mean radiant temperature, solar radiation