摘要 针对目前烟囱防腐领域所使用的发泡陶瓷砖,选取国内具有代表性的两种不同品牌的发泡陶瓷砖产品,在模拟烟囱工况下进行了浸泡腐蚀试验及热振试验。试验结果表明,不同品牌的发泡陶瓷砖在性能上有较明显的差异。耐蚀性能方面,在质量分数为5%、温度为70℃的混酸溶液中浸泡10d后,两者的腐蚀增长率分别为1.02%、73.89%;吸水率方面,在70℃的蒸馏水中浸泡10d后,吸水率分别为0.17%、22.46%;二者都具有较好的热振性能,加热到200℃再空冷到40℃的热振试验中,经历10个循环后无变化。 Performance of two types of foamed ceramic bricks used in chimney anti-corrosion is studied under stimulated situations which contain soaking test and thermal shock test.The test results show that the performance of foamed ceramic brick manufactured by deferent factories is deferent obviously.Weight gain rate after 10d test soaking in a 5% mixed acid solution of 70℃ is 1.02% and 73.89%.Water absorption rate after 10d test soaking in distilled water of 70℃ is 0.17%,22.46%.Two types of foamed ceramic bricks all have good performance about thermal shock which is conducted for 10 times baking to 200℃ then cooling in air to 40℃ and there is no variety.
出处 《工程与试验》 2013年第4期49-50,77,共3页 Engineering and Test
关键词 发泡陶瓷 烟囱防腐 浸泡试验 热振 吸水率 foamed ceramic chimney anti-corrosion soaking test thermal shock water absorp-tion rate
  • 相关文献

参考文献5

二级参考文献21

  • 1孙宏斌,雷艳红.火电厂脱硫“湿烟囱”防腐蚀内衬结构设计[J].陕西建筑,2009(12):7-9. 被引量:4
  • 2GB50300-2001建筑工程施工质量验收统一标准[S].北京:中国建筑工业出版社,2001.
  • 3GB50051-2002烟囱设计规范[S].北京:中国计划出版社,2003.
  • 4郝吉明 王书肖 陆永琪.燃煤二氧化硫污染控制技术手册[M].北京:化学工业出版社,2002..
  • 5曾庭华 杨华 王斌.湿法烟气脱硫系统的安全性及优化[M].北京:中国电力出版社,2003..
  • 6GB50068-2001建筑结构可靠度设计统一标准[S].北京:中国建筑工业出版社,2001
  • 7RandojphW.Snook 杜振华译.高烟囱的改造关键在内衬[J].POWER,1992,(2).
  • 8电力工业部西北电力设计院.火力发电厂土建结构设计技术规定[S].DL 5022-93行业标准.水利电力出版社,1994年1月.
  • 9张祖涛.排放SO2烟气的烟囱形式选择[C].中国腐蚀与防护学会建筑工程专业委员会第二次学术会议论文选编.
  • 10GB50046-2008.工业建筑防腐设计规范[S].北京:中国计划出版社,2008.