期刊文献+

直接膨胀式地源热泵设计工况探讨 被引量:2

Discussion on design conditions for direct-expansion ground-source heat pump
下载PDF
导出
摘要 对直接膨胀式地源热泵的运行工况进行了测试和分析.结果表明:直接膨胀式地源热泵压缩机不能直接按名义工况的制冷量或制热量来选型,而是在考虑冷热负荷不同的地区特性,以全年主要的运行工况为选型依据.夏季单U埋地换热器的出口温度按全年平均空气温度加上5~8℃来设计;冷凝温度按全年平均空气温度加上11~ 13℃来确定;蒸发温度按标准空气源热泵(AHRI)的名义工况7.2℃来确定. The operation conditions of direct-expansion ground-source heat pump (DX-GSHP) sys- tems were analysed. The results indicate that the selection of DX-GSHP compressor cannot be fully based on standard rating condition. The annual main operation mode can serve as a basis for equip- ment selection while considering the load difference of the areas and zones. The designed outlet-tem- perature of the single U-bend loop ground heat exchanger can be set at annual average air tempera- ture plus 5 - 8 ℃, whereas the condensing temperature is set at annual average air temperature plus 11 -13 ℃. The evaporating temperature is set at 7.2 ℃, the nominal refrigeration capacity testing working condition of summer for air source heat pump unit specified by Air-conditioning, Heating and Refrigeration Institute (AHRI).
出处 《福建工程学院学报》 CAS 2013年第6期556-560,共5页 Journal of Fujian University of Technology
基金 福建省科技厅科技重大专项(GY-Z09004) 福建工程学院科研启动基金(GY-Z13107)
关键词 直接膨胀 地源热泵 设计工况 蒸发温度 冷凝温度 direct expansion ground-source heat pump design condition evaporating temperature condensing temperature
  • 相关文献

参考文献13

  • 1Halozan H. Direct-expansion ground-coupled heat pumps[J].EA HPC Newsletter,2005,(04):30-32.
  • 2Freund E A,Whitlow G S. Earth source heat pumps:characteristics,design and operation[J].AIEE Journal,1959,(07):540-551.
  • 3Coogan C H. Heat transfer rate[J].{H}Mechanical Engineering,1949,(06):495-498.
  • 4J R.Goulbum,J Fearon. Deep ground coil evaporators for heat pumps[J].{H}Applied Energy,1978,(04):193-213.
  • 5J R.Goulburn,J Fearon. Domestic heat pump with deep hole ground source evaporaton[J].{H}Applied Energy,1983,(02):99-113.
  • 6Mei V C. Experimental analysis of direct-expansion ground-coupled heat pump systems[J].{H}Ashrae Transactions,1990,(02):821-828.
  • 7Johnson W S. Field tests of two residential direct exchange geothermal heat pumps[J].{H}Ashrae Transactions,2002,(02):99-106.
  • 8王晓涛,闫桂兰,郑鹏,马重芳.直接膨胀式土壤耦合热泵系统研究进展[J].暖通空调,2007,37(11):22-29. 被引量:10
  • 9贾绍强.直接膨胀式土壤源热泵试验研究及地下换热系统分析[D]{H}长沙:湖南大学,200821-34.
  • 10Kavanaugh S. Design considerations for ground and water source heat pumps in the southern climates[J].{H}Ashrae Transactions,1995,(01):1139-1148.

二级参考文献45

  • 1中国建筑科学研究院.GB 50366-2009地源热泵系统工程技术规范[S].北京:中国建筑工业出版社,2009.
  • 2Kavaugh S.Design considerations for ground and water source heat pumps in the southern climates[G] //ASHRAE Trans,1995,101(1):1139-1148.
  • 3Jr Coogan C H.Heat transfer rate[J].Mechanical Engineering,1949,71(6):495-498.
  • 4Hart D P.Heat pump system:United States,5038580[P].1991-08-13.
  • 5Mei V C.Experimental analysis of direct-expansion ground-coupled heat pump systems[G] //ASHRAE Trans,1990,96(2):821-828.
  • 6Freund E A,Whitlow G S.Earth,source heat pumps:characteristics,design,and operation[J].Jan AIEE Journal,1959,59(7):540-551.
  • 7Crompton P, Wu Y. Energy consumption in China: Past trends and future direction [J]. Energy Economics, 2005, 27(1) : 195 - 208.
  • 8Spitler J 13. Ground-source heat pump system research--Past, present and future [J]. HVAC R Research, 2005, 11(2): 165-167.
  • 9Yang Weibo, Ming Hengshi, Hua Dong. Numerical simulation of the performance of a solar-earth source heat pump system [ J ]. Applied Thermal Engineering, 2006, 26(17/18):2367-2376.
  • 10Wang Huajun, Qi Chengying. Performance study of underground thermal storage in a solar-ground coupled heat pump system for residential buildings [J]. Energy and Buildings,2008,40(7): 1278-1286.

共引文献9

同被引文献16

引证文献2

二级引证文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部