某厂2#主变故障跳闸事故分析 被引量:3

Analysis on the Trip Accident of 2# Main Transformer Switch in one Factory
下载PDF
导出
摘要 分析主变突然跳闸原因,对其变压器油参数,高压线圈直阻、介损、绕组变形试验等进行分析,查找故障发生的原因,提出故障发生的原因是由于密封垫圈变形导致变压器油中进水,绝缘降低发生C相匝间短路并针对暴露出的问题提出防范措施. The parameters of transformer oil, high voltage coil DC resistance, dielectric loss, and winding deformation test were carried out to find out the reason of trip accident of 2# main transformer switch. It is verified that water penetrate into transformer oil because of sealing gasket deformation, corresponding worsened insulation induced intertum short circuit of the C phase winding. Finally, the precautionary measures are proposed in this paper.
作者 刘常碧
出处 《沈阳工程学院学报(自然科学版)》 2014年第1期58-60,77,共4页 Journal of Shenyang Institute of Engineering:Natural Science
关键词 主变压器 匝间短路 垫片 积水 Main transformer Interturn short circuit Shim Water accumulation
  • 相关文献

参考文献3

二级参考文献3

  • 1变压器制造技术丛书编审委员会.变压器试验[M].北京:机械工业出版社,2005.
  • 2DL/T596-1996.电力设备预防性试验规程[S].[S].,1996..
  • 3钨伟民.高压电气设备现场试验技术365问[M].北京:水利电力出版社,1996.

共引文献11

同被引文献9

引证文献3

二级引证文献3