期刊文献+

基于CDEGS的金属构架雷击电磁分析 被引量:6

Lightning Electromagnetic Analysis of Metal Structures Based on CDEGS
下载PDF
导出
摘要 为研究金属构架遭雷击时的电磁特点及其影响因素,并应用于实际建构筑物的工程计算分析,提出将CDEGS软件应用于于这种计算,并利用电路法、有限元法和实验数据的对比验证了其可行性。文中还对金属构架内雷击电磁特点和部分影响因素进行了分析,得到离雷击点越远的垂直导体分流系数越小、各导体之间区域的磁场强度远小于导体附近等结论,并给出了雷击建构筑物时室内电子设备电磁防护的一些注意点。最后对一通信塔进行了实例分析。综上,CDEGS可应用于雷击室内电磁环境评估,具有一定的科研和业务应用价值。 In order to research lightning electromagnetic distribution characteristics of metal structures and its influencing factors on one hand, and on the other hand to give engineering calculation on actual architectural structures, we put forward application of CDEGS software in the calculation and use the result of circuit method, FEM and corresponding experiment to verify its feasibility. This paper is also aimed at analyzing lightning electromagnetic distribution characteristics of metal structures and its influencing factors. It comes to the conclusion that the farther away from the lightning strike point the smaller shunting coefficient of vertical conductor it will be; magnetic strength in the area among conductors is far less than that near conductors, etc. Then some notes are given on electromagnetic protection of electronic equipment indoors when architectural structures are struck by lightning. Finally, a case analysis is given on a communication tower. In conclusion, CDEGS can be applied to evaluation of lightning electromagnetic environment indoors, with certain value of scientific research and business application.
出处 《高压电器》 CAS CSCD 北大核心 2014年第2期35-41,共7页 High Voltage Apparatus
基金 江苏省社会发展项目(BE2009693)~~
关键词 CDEGS 有限元法 直击雷 分流系数 磁场强度 CDEGS finite element method direct lightning shunting coefficient magnetic strength
  • 相关文献

参考文献21

  • 1HILL R D. Note on vulnerability of computers to lightning [EB/OL] http://oai.dtic.mil/oai/oai?verb=get Record & metada- ta Prefix =html &i dentifier=AD0722675.AD0722675,1971- 04-18/2013-08-11.
  • 2ORLANDI A,SCHIETROMA F. Attenuation by a light- ning protection system of induced voltages due to direct strikes to a building[J]. IEEE Trans. on EMC, 1996,38(1): 43-50.
  • 3ORLANDI A, MAZZETTI C,FLISOWSKI Z, et al.System- atic approach for the analysis of the electromagnetic environment in side a building during a lightning strike [J]. IEEE Transactions on Eleetr0magnetie Compatibility, 1998,40(4):521-535.
  • 4SARTORI C F,CARDOSO J R,ORLANDI A. Transient in- duced voltage computation in a high building struck by light-ning[J]. IEEE Trans. on Magnetics, 1998,34(5): 2815-2818.
  • 5KATO J,KAWANO H. Investigation of lightning surge current induced in reinforced concrete buildings by direct strikes[J]. IEEE Int. Syrup. on EMC,2001(2): 1009-1014.
  • 6DU Y,CHEN Shuiming,BURNETF J. Experimental and numerical evaluation of surge current distribution in building during a direct lightning stroke[J]. Transaction Hong Kong Institution of Engineers,2001,8(1): 1-6.
  • 7戴传友.雷击金属结构物时近区磁场分布的研究[D].上海:上海交通大学.1998.
  • 8张小青,陈水明.直接雷击时高层建筑物内暂态磁场的计算[J].中国电机工程学报,2001,21(1):40-43. 被引量:20
  • 9林福昌,姚宗干,蒋政龙.雷击建筑物时电流分布的计算[J].高电压技术,1998,24(1):56-58. 被引量:17
  • 10巩学海,何金良,李雨.变电所的瞬态电磁环境分析[J].高压电器,2009,45(5):39-43. 被引量:19