期刊文献+

Influence of infiltration on energy consumption of a winery building

Influence of infiltration on energy consumption of a winery building
原文传递
导出
摘要 With the wide use of light steel structure in industrial buildings, some problems such as air leakage, water dripping and condensation and so forth occur during the construction and operation phases. Through the onsite testing of a winery building in Huailai County, Hebei Province in China, the influence of infiltration on energy consumption in industrial buildings was studied. The pressurization test method and moisture condensation method were used to test the infiltration rates. The results show that the winery building is twice as leaky as normal Chinese buildings and five times as leaky as Canadian buildings. The energy use simulation demonstrates that the reduction of the infiltration rate of the exterior rooms to 1/3 and the interior rooms to 1/2 could help decrease a total energy consumption of approximately 20% and reduce a total energy cost of approximately $ 225000. Therefore, it has a great potential to reduce the energy consumption in this type of buildings. Enforcement of the appropriate design, construction and installation would play a significant role in improving the overall performance of the building. With the wide use of light steel structure in industrial buildings, some problems such as air leakage, water dripping and condensation and so forth occur during the construction and operation phases. Through the onsite testing of a winery building in Huailai County, Hebei Province in China, the influence of infiltration on energy consumption in industrial buildings was studied. The pressurization test method and moisture condensation method were used to test the infiltration rates. The results show that the winery building is twice as leaky as normal Chinese buildings and five times as leaky as Canadian buildings. The energy use simulation demonstrates that the reduction of the infiltration rate of the exterior rooms to 1/3 and the interior rooms to 1/2 could help decrease a total energy consumption of approximately 20% and reduce a total energy cost of approximately $ 225000. Therefore, it has a great potential to reduce the energy consumption in this type of buildings. Enforcement of the appropriate design, construction and installation would play a significant role in improving the overall performance of the building.
出处 《Frontiers in Energy》 SCIE CSCD 2014年第1期110-118,共9页 能源前沿(英文版)
关键词 industrial building air change rate pressur-ization test method moisture condensation method energycost industrial building, air change rate, pressur-ization test method, moisture condensation method, energycost
  • 相关文献

参考文献1

二级参考文献16

  • 1NEGRAO C O R. Integration of computational fluid dynamic with building thermal and mess flow simulation [J]. Building and Environmental, 1998, 27: 155-165.
  • 2ZHAI Zhi-qiang, CHEN Qing-yan, HAVES P. On approach to couple energy simulation and computational fluid dynamic programs [J]. Building and Environmental, 2002, 37: 857-864.
  • 3ZHAI Zhi-qiang, CHEN Qing-yan. Solution characters of iterative coupling between energy simulation and CFD programs [J]. Energy and Building, 2003, 35: 493-505.
  • 4ZHAI Zhi-qiang, CHEN Qing-yan. Performance of coupled building energy and CFD simulations [J]. Energy and Building, 2005, 37: 333-344.
  • 5ZHAI Zhi-qiang, CHEN Qing-yan. Sensitivity analysis and application guides for integrated building energy and CFD simulation [J]. Energy and Building, 2006, 38: 1060--1068.
  • 6DJUNAEDY E, HENSEN J, LOOMANS M. External coupling between CFD and energy simulation: implementation and validation [J]. ASHRAE Transactions, 2005: 612-624.
  • 7CRAWLEY D B. Contrasting the capabilities of building energy performance simulation programs [J]. Building and Environment, 2008, 43: 661-673.
  • 8ARIAS D A. Advance on the coupling between a commercial CFD package and a component-based simulation program [C]// Second National IBPSA-USA Confgrence. Cambridge MA. 2006:231-237.
  • 9ANSYS. ANSYS/FLUENT 12 [M]. ANSYS Japan Ltd. 2009.
  • 10KLEIN S A, BECKMAN W A, MITCHELL J W, et al. TRNSYS 17: A Transient system simulation program, SEL [D]. Madison, USA: University of Wisconsin, 2006,.

共引文献4