摘要
为了解决水源热泵系统回灌过程中出现的问题,选择典型项目开展回灌监测工作,通过对各井水位、水量的监测,获得了7年的监测数据,确定了各井的回灌能力,监测结果表明:项目运行的前3年回灌系统处于最佳工作状态,但系统运行6年后,各井回灌量累计衰减超过60%。
This paper chooses a typical project to make a monitoring plan. After 7 years' monitoring, all the recharge wells' water level and the quality of water has been recorded after every running season. It is used to determine every wells' recharge capacity. The result shows the first 3 years the recharge system was at an optimal state. However after the system running 6 years, the well recharge has decreased over 60%.
出处
《山西建筑》
2014年第9期151-153,共3页
Shanxi Architecture
关键词
水源热泵
回灌量
水位
监测
water source heat pump, recharge, mater level, detection