期刊文献+

利用交流电直流分量对电网数据进行精确采集与仿真

A accurate acquisition and simulation to the power grid data of using AC and DC component
下载PDF
导出
摘要 本文提出了一种利用交流电的直流分量对电网数据进行采集的方法,通过算法论证和仿真结果实现了电网数据的精确采集。首先将三相电源的相电压信号(标准值为220 V/380 V、50 Hz)调理成小幅度的可以测试到的0~5 V交流电压;然后采用全波整流电路进行信号整流;再采用硬件滤波与软件滤波相结合的办法进行信号滤波;最终得出信号的直流分量。并根据电路搭建了仿真模块,从实验平台来验证了理论的可行性和准确性。 This paper presents a acquisition method to the DC component of grid data by using alternating current, The algo- rithm and simulation results achieved grid data accurately. Firstly, the phase voltage signal of three - phase power (standard values for 220V/380V, 50Hz) regulate into small amplitude and 0 ~ 5V AC voltage which could test to,then use the full wave rectifier circuit for signal rectification ; and use the method of combining hardware filter and software filter for signal ill- tering; finally get DC component of the signal. According to the circuit this paper built simulation module, and verify the feasibility and accuracy of the theory from the experimental platform.
出处 《现代机械》 2014年第2期69-72,76,共5页 Modern Machinery
关键词 数据采集 智能化 信号调理 Multisim11 the data collection intelligentialize signal conditioning Muhisiml 1