摘要 某电厂锅炉补给水阴双室固定床出水硬度超标。通过现场数据分析发现,原因为阳床在反复试投运的过程中,已经深度失效,导致阳床出水带有硬度,再进入强碱树脂层时,硬度产生沉淀,并沉积在阴床内,在投运阴床时硬度缓慢释放。通过酸碱浸泡的方法对阴树脂进行复苏,复苏后的阴床出水水质合格。 The effluent from fixed double chamber anion bed in a power plant has high level hard ness, which has overstandard. The reasons like raw water leaking into the anion bed, alkali being polluted and cation resin leaking into the anion bed were excluded. The field test data show the deep failure of cation bed during its repetitive commissioning is the actual cause. Then when the water from the cation bed flows into the alkaline resin layer, the hardness will deposit on the ani on bed and slowly release when the anion bed runs. Thus, the acid and alkali immersion methods were employed to regenerate the anion resin. After that, the effluent from fixed double chamber anion bed met all standard requirements.
机构地区 云南电力研究院
出处 《热力发电》 CAS 北大核心 2014年第4期113-115,共3页 Thermal Power Generation
关键词 阴双室固定床 硬度 树脂 失效 再生 fixed double chamber anion bed hardness resin failure regeneration
  • 相关文献

参考文献7

二级参考文献8

  • 1朱兴宝.降低阴床出水含硅量的探讨.水处理技术,1985,(1):51-53.
  • 2朱兴宝.阴双层床树脂混层的研究.净水技术,1985,4(3):1-4.
  • 3朱兴宝.阴双层床中选择两种树脂最佳配比的计算方法.湖北电力技术,1984,(3):43-47.
  • 4冯敏,工业水处理技术,1992年,336页
  • 5施燮钧,王泉聚,肖作善.热力发电厂水处理[M].北京:中国电力出版社,1996.
  • 6Drew N J.Evaluation of degassed after-cation-exchange conductivity techniques,2004(06).
  • 7李志成,王应高.在线氢电导率表离子交换柱附加误差研究[J].热力发电,2011,40(3):20-23. 被引量:25
  • 8田文华,郭安祥,马海燕.离子交换树脂污染原因分析及复苏方法[J].西北电力技术,2000(5):4-7. 被引量:11