期刊文献+

基于暂态主频分量的配电网单相接地故障测距研究

A Study on the Ranging of the Single-phase Earth Fault of the Distribution Network Based on Transient Basic Frequency Components
下载PDF
导出
摘要 提出一种利用暂态主频量的单端测距算法,并分别通过频域法和时域法的求解,得到故障距离。EMTP仿真结果表明,其测距的最大相对误差小于0.231%,平均测距误差小于20 m,能够满足实际工程需求。 This essay presents a single-ended ranging algorithm based on transient basic frequency components. The fault distances can be obtained by using the frequency domain and time domain methods to get relevant solutions. The EMTP simulation results show that the maximum relative error of the algorithm in ranging is less than 0.231% and the average error is less than 20 meters, so it can meet the requirements of practical engineering.
出处 《重庆电力高等专科学校学报》 2014年第2期40-44,共5页 Journal of Chongqing Electric Power College
关键词 单相接地 暂态信息 主频 拉氏变换 单端测距 single-phase earth transient information basic frequency Laplace transform single-ended raging