通过现场试验的方法研究了智能送风地板解决数据机房局部高热的效果,以及智能送风地板使用前后空调的节能效果和机房的PUE值变化情况。试验证明智能送风地板能够降低机柜的排风温度,解决机房的局部高热问题,使机房内各区域温度分布均匀,从而可在一定程度上提高机房环境温度、减少空调系统能耗、降低机房PUE值。
This paper research the effect of intelligent supply floor solve partial heat of IDC rooms through field experiment, and the effect of air-condition energy-saving,the change of PUE after the use of intelligent supply floor. The results indicated that the intelligent supply floor can reduce the exhaust temperature of communication cabinet and solve partial heat of IDC rooms, achieved the temperature evenly distributed in IDC rooms. Thereby the environment temperature can be elevated to a certain extent, and consequently. The energy of air-condition and PUE of IDC rooms will be reduced.