期刊文献+

A red water occurrence in drinking water distribution systems caused by changes in water source in Beijing, China: mechanism analysis and control measures 被引量:8

A red water occurrence in drinking water distribution systems caused by changes in water source in Beijing, China: mechanism analysis and control measures
原文传递
导出
摘要 A red water phenomenon occurred in several communities few days after the change of water source in Beijing, China in 2008. In this study, the origin of this problem, the mechanism of iron release and various control measures were investigated. The results indicated that a significant increase in sulphate concentration as a result of the new water source was the cause of the red water phenomenon. The mechanism of iron release was found that the high-concentration sulphate in the new water source disrupted the stable shell of scale on the inner pipe and led to the release of iron compounds. Experiments showed that the iron release rate in the new source water within pipe section was over 11-fold higher than that occurring within the local source water. The recovery of tap water quality lasted several months despite ameliora- tive measures being implemented, including adding phosphate, reducing the overall proportion of the new water source, elevating the pH and alkalinity, and utilizing free chlorine as a disinfectant instead of chloramine. Adding phosphate was more effective and more practical than the other measures. The iron release rate was decreased after the addition of 1.5 mg. L-1 orthophosphate- P, tripolyphosphate-P and hexametaphosphate-P by 68%, 83% and 87%, respectively. Elevating the pH and alkalinity also reduced the iron release rate by 50%. However, the iron release rate did not decreased after replacing chloramine by 0.5-0.8 mg. L-1 of free chlorine as disinfectant. A red water phenomenon occurred in several communities few days after the change of water source in Beijing, China in 2008. In this study, the origin of this problem, the mechanism of iron release and various control measures were investigated. The results indicated that a significant increase in sulphate concentration as a result of the new water source was the cause of the red water phenomenon. The mechanism of iron release was found that the high-concentration sulphate in the new water source disrupted the stable shell of scale on the inner pipe and led to the release of iron compounds. Experiments showed that the iron release rate in the new source water within pipe section was over 11-fold higher than that occurring within the local source water. The recovery of tap water quality lasted several months despite ameliora- tive measures being implemented, including adding phosphate, reducing the overall proportion of the new water source, elevating the pH and alkalinity, and utilizing free chlorine as a disinfectant instead of chloramine. Adding phosphate was more effective and more practical than the other measures. The iron release rate was decreased after the addition of 1.5 mg. L-1 orthophosphate- P, tripolyphosphate-P and hexametaphosphate-P by 68%, 83% and 87%, respectively. Elevating the pH and alkalinity also reduced the iron release rate by 50%. However, the iron release rate did not decreased after replacing chloramine by 0.5-0.8 mg. L-1 of free chlorine as disinfectant.
出处 《Frontiers of Environmental Science & Engineering》 SCIE EI CAS CSCD 2014年第3期417-426,共10页 环境科学与工程前沿(英文)
关键词 iron release drinking water distribution system sulphate PHOSPHATE red water control waterquality stability iron release, drinking water distribution system, sulphate, phosphate, red water control, waterquality stability
  • 相关文献

参考文献1

二级参考文献8

  • 1牛璋彬,王洋,张晓健,何文杰,韩宏大,阴沛军.某市给水管网中铁释放现象影响因素与控制对策分析[J].环境科学,2006,27(2):310-314. 被引量:19
  • 2Berg R L,Jensen T φ,Bennedsen L,et al.Investigation of introducing water from an artificial recharge plant to an existing groundwater distribution system[J].Water Supply,2005,5(1):25-32.
  • 3国家环境保护总局.水和废水监测分析方法[M].(第三版).北京:中国环境科学出版社,2002.177-285.
  • 4Sarin P,Snoeyink V L,Bebeel J,et al.Physical-chemical characteristics of corrosion scales in old iron pipes[ J ].Water Research,2001,(12):2961-2969.
  • 5Sarin P,Jonathan A Clement,Vernon L Snoeyink,et al.Iron release from corroded,unlined cast-iron pipe[J].American Water Works Association,2003,(11):85-96.
  • 6Kuch A.Investigations of the Reduction and Re-oxidation Kinetics of Iron (Ⅲ) Oxide Scale Formed in Waters[ J ].Corrosion Science,1988,28(3):221-31.
  • 7Sontheimer H,Kolle W,Snoeyink V L.The Siderite Model of the Formation of Corrosion-resistant Scales[J].AWWA,1981,73(11):572-579.
  • 8Syedabdul Vakebl Imran.Effect of Water Quality on Red Water Release in Iron Drinking Water Distribution System[D].Florida:the Department of Civil and Environmental Engineering in the College of Engineering and Computer Science at the University of Central Florida,2003.