期刊文献+

304奥氏体不锈钢管道焊缝氯离子腐蚀渗漏浅析 被引量:7

The Probe of Corrosion Leakage in Welding seam by chloride Ion of Austenitic Stainless Steel 304 Pipe
下载PDF
导出
摘要 上海松江某电子工程项目,工业自来水系统和冲身洗眼器系统的管道安装,经过验收→使用→出现渗漏→整改→使用→又出现渗漏。对此,依据具体情况进行分析研究,从查证资料显示和该工程上的管道渗漏实际情况来看,渗漏的原因在于自来水中的氯离子对奥氏体不锈钢腐蚀所致。 The popes for industrial tap water system and body and eye wash system were installed in an electronic manufacturer in Songjiang, Shanghai, which experienced acceptamce, operation, leakage, repair, operation, and leakage ge once again. The reason of leakage was found caused by corrison of Austenitic ss from chloride ion in tap water, as shown through examination of actual leakage in pipe and data retrieve.
出处 《洁净与空调技术》 2014年第2期73-76,共4页 Contamination Control & Air-Conditioning Technology
关键词 奥氏体不锈钢 氩弧焊接 氯离子 孔蚀 渗漏 Austenitic stainless steel Argon-arc welding Chloride ion Hole corrosion
  • 相关文献

参考文献6

  • 1左景伊,左禹.腐蚀数据与选材手册[M].北京:化学工业出版社,2008:63.
  • 2张远声.腐蚀与破坏事故100例[M].北京:化学工业出版社,2001.
  • 3GB50235-97,工业金属管道工程施工及验收规范[S].
  • 4GB 50236-98,现场设备、工业管道焊接工程施工及验收规范[S].
  • 5岭澳核电站循环水过滤系统316L不锈钢管道点腐蚀的理论分析[G].中国核电论坛,2005.
  • 6河南石油勘察设计研究院.不锈钢波纹管换热器的腐蚀与防护[G].南阳:2006.