期刊文献+

电子信息系统雷击空间磁场强度研究 被引量:2

Study on Magnetic Intensity in Lightning Stroke Space of Electronic Information System
下载PDF
导出
摘要 应用雷电监测网资料对雷电直接击于建筑物或击于建筑物附近所产生的空间磁场强度进行估算,得出在引下线周围1--5m范围磁场强度衰减值,并估算出电子信息系统机房应加装的屏蔽网格宽度。 The magnetic intensity caused by direct lightning stroke on buildings or neighbors is estimated according to data from the lightning detection network, thus obtaining the attenuation value of magnetic intensity within a range of 1 to 5m around down-conductor system and estimating the width of a shielding grid installed on an electronic information system room.
出处 《建筑电气》 2014年第6期34-38,共5页 Building Electricity
关键词 磁场分布 安全空间 屏蔽网格宽度 雷电流幅值 分流系数 引下线 屏蔽系数 防雷设计 magnetic field distribution security space width of shielding grid amplitude of lightning current shunt coefficient down-conductor system shielding coefficient design of protection against lightning
  • 相关文献

参考文献8

  • 1梅贞,陈水明,顾勤炜,黄歆章.1998~2004年全国雷电灾害事故统计[J].高电压技术,2007,33(12):173-176. 被引量:37
  • 2清华大学,起草.GB/ T 21714. 4 - 2008 / IEC62305 -4: 2006雷电防护第4部分:建筑物内电气和电子系统[S].北京:中国标准出版社,2008.
  • 3中国中元国际工程公司.GB50057-2010建筑物防雷设计规范[S].北京:中国计划出版社,2011.
  • 4中国建筑标准设计研究院,四川中光防雷科技股份有限公司,主编.GB 50343 -2012建筑物电子信息系统防雷技术规范[S].北京:中国建筑工业出版社,2012.
  • 5华北计算技术研究所,等.GB/T2887-2011电子计算机场地通用规范[S].北京:中国标准出版社,2011.
  • 6四川中光高科产业发展集团,起草.GB/T21714. 1 - 2008 / IEC 62305 - 1 : 2006 雷电防护第 1 部分:总则[S].北京:中国标准出版社,2008.
  • 7广东省防雷中心,起草.GB/T21714. 2-2008/ IEC 62305 - 2: 2006 雷电防护第2部分:风险管理[S].北京:中国标准出版社,2008.
  • 8中国电信集团湖南省电信有限公司.GB/T21714.3-2008/IEC62305-3:2006雷电防护第3部分:建筑物的物理损坏和生命危险[S].北京:中国标准出版社,2008..