摘要 核电厂换料水箱是保障反应堆事故工况下,为设备冷却供水的设备之一。研究发现,国内外核电厂换料水箱底板有出现裂纹,甚至发生泄漏的案例。为了更好的对换料水箱实施检测,有必要筛选出无损检测的重点区域,获知裂纹的验收尺寸。因此本文从应力分析的角度,对核电厂换料水箱进行了有限元模拟,分析了应力集中区域;并通过应用线弹性断裂力学确定了换料水箱底板的临界裂纹尺寸。为后续现场检测、评定工作提供依据。 In-Containment refueling water storage tank (IRWST) is used to store enough dilute boric acid for cooling reactor vessel in some accidents. It is found that several IRWSTs leak water from the tank bottom plant, home and abroad. For effective inspection of tank, it' s better to determine the weakness field and evaluate critical crack size. This paper used ABAQUS finite element commercial code establish model of IRWST, to analyze the bottom plant stresses, and used elastic fracture mechanic to calculate critical crack sizes of IRWST. The results provide some guidances for executing inspection and evaluation for the tank.
出处 《全面腐蚀控制》 2014年第6期29-32,共4页 Total Corrosion Control
关键词 换料水箱 裂纹 应力分析 临界裂纹尺寸 IRWST crack stress analysis critical crack size
  • 相关文献

参考文献6

  • 1苗学良,张维,徐伟.大型储罐器壁腐蚀减薄的自动超声扫查[J].腐蚀与防护,2013,34(10):954-956. 被引量:1
  • 2AFCEN, RSE-M. in-service inspection rules for the mechanical components of PWR NUCLEAR ISLANDS[S], Pairs, EDF, 1997.
  • 3T.J.Jordan. Evaluation of the Refueling Water Storage Tank Bottom Plate Crack[N]. NRC Technical Report, 1999.
  • 4卢岳川,吴万军,臧峰刚,孙英学,刘文进.大亚湾核电站换料水箱底板渗漏分析与评估[J].原子能科学技术,2008,42(S2):648-651. 被引量:5
  • 5聂勇,刘鸿运,李培宁等.NB/T20013含缺陷核承压设备完整性评定[S].国家能源局,2010.
  • 6陈钢,钟群鹏,李培宁等.GB/T19624在用含缺陷压力容器安全评定[S].中国国家标准管理委员会,2004.