期刊文献+

热虹吸器对变压器油中糠醛测定的影响 被引量:2

Study of the Effect of the Thermosiphon Bypass’s Runing on the Furfurol Content in the Transformer Oil
下载PDF
导出
摘要 模拟研究了变压器热虹吸器循环系统中吸附剂对变压器油中糠醛组分的吸附特性 ,得出其吸附作用规律 ,据此可得到由于变压器中固体绝缘老化分解产生并且溶解于油中糠醛质量的实际值 ,解决了变压器油中糠醛质量浓度检测失真的问题 。 The properties that the absorbent absorbs the furfurol in the transformer oil is studied by the simulative thermosiphon bypass system and the absorbing features is given. With the regulation,we can calibrate the furfurol content in the transformer oil, and obtain the true furfurol content which is produced by solid insulation’s aging and dissolved in the oil, and can accurately judge the life of solid insulation in the transformer.
出处 《高电压技术》 EI CAS CSCD 北大核心 2001年第1期59-61,共3页 High Voltage Engineering
关键词 热虹吸器 吸附剂 糖醛 测定 变压器油 thermosiphon bypass absorbent furfurol
  • 相关文献

参考文献3

  • 1吉林大学.物理化学[M].北京:人民教育出版社,1979.158-178.
  • 2叶振华,化工吸附分离过程,1992年
  • 3吉林大学,物理化学,1979年

共引文献1

同被引文献27

  • 1彭宁云,文习山,王一,陈江波,柴旭峥.基于线性分类器的充油变压器潜伏性故障诊断方法[J].中国电机工程学报,2004,24(6):147-151. 被引量:35
  • 2宋斌,杨玲君,于萍,罗运柏,文习山.多参数关联分析研究变压器油的热老化特性[J].高电压技术,2005,31(1):17-19. 被引量:13
  • 3王万华.变压器绝缘老化诊断中应注意的问题[J].高电压技术,1995,21(3):79-82. 被引量:25
  • 4Faber J, Pichon A. Deteriorating processes and products of paper in oil application to transformers[C]// CIGRE Conference on Large High Voltage Electric Systems. Paris, France:CIGRE, 1960: 137.
  • 5Noirhomme B, Sparling B, Aubin J, et al. A practical method for the continuous monitoring of water content in transformer solid insulation[C]// Proceedings of EPRI Substation Equipment Diagnostics Conference Ⅷ. New Orleans, USA: EPRI, 2000: 201-214.
  • 6Rapp K J, Luksich J. Reaction rates of paper aged in natural esier dielectric fluid[C]// 2001 Annual Report Conference on E lectrical Insulation and Dielectric Phenomena. Kitchener, Ontar rio, Canada: Institute of Electrical and Electronics Engineers Inc, 2001: 209-212.
  • 7Shroff D H, Stannett A W. Review of paper aging in power transformers[J]. IEE Proceedings--Part C: Generation, Transmission and Distribution, 1985, 132(6): 312- 319.
  • 8Zou X, Uesaka T, Gurnagul N. Prediction of paper permanence by accelerated aging, I : Kinetic analysis of the aging process [J]. Cellulose, 1996, 3(1): 243-267.
  • 9Michel D. A review of fault s detectable by gas2in2oil analysis in transformers [J]. IEEE Electrical Insulation Magazine,2002, 18(3): 8217.
  • 10Gardez C A R, Vladimiro M. Knowledge discovery in neural networks with application to transformer failure diagnosis[J]. IEEE Trans on Power Systems, 2005, 20(2):717-724.

引证文献2

二级引证文献10