配电网接地故障负序电流分布及接地保护原理研究 被引量:150

STUDY FOR NEGATIVE SEQUENCE CURRENT DISTRIBUTING AND GROUND FAULT PROTECTION IN MIDDLE VOLTAGE POWER SYSTEMS
下载PDF
导出
摘要 配电网发生最多的故障是接地故障 ,如何准确地检测并隔离接地故障线路 ,成为小电流接地系统实现配电自动化的一个重要研究课题。传统的故障选线采用比较零序电流方法 ,不便在馈线保护中实现及现场终端单元 (FTU )上安装。该文对接地故障负序电流分布进行分析 ,提出负序电流接地保护原理并通过EMTP仿真分析验证 。 How to detect and isolate earth faulty section is an important subject to realize distribution automation in ineffectively grounded systems. Traditional methods for faulty feeder protection based on comparing zero sequence currents are difficult to satisfy the requirement of distribution automation. Negative sequence current.distributing is discussed and new principle for faulty feeder protection based on negative sequence current is presented in this paper. The principle is verified by EMTP simulator and the prototype is developed, which has been tested in dynamic power system model.
出处 《中国电机工程学报》 EI CSCD 北大核心 2001年第6期84-89,共6页 Proceedings of the CSEE
关键词 配电网 接地故障 负序电流 接地保护 小电流接地系统 distribution automation fault detection protective relaying