期刊文献+

汉川电厂锅炉受热面泄漏整治 被引量:5

Elimination of Leakage of Boiler Heating Surface in Hanchuan Power Plant
下载PDF
导出
摘要 针对汉川电厂300 MW电站锅炉存在的过热器爆管和受热面磨损泄漏等问题,进行了模化试验和现场试验研究,提出燃烧器“反切”改造,加装导流板、阻流板及防磨板等改造措施,使锅炉运行可靠性大大提高,取得了很好的经济效益。 The bursting of superheater tubes and wearing-leakage of heating surface etc. problems existed on the 300 MW boilers in Hanchuan Power Plant.Through the modeling test and on-site experiment employing ″counter-tangent″burners and installing guiding plates choke plates and wear prevention plates etc. retrofitting measures were put forward and fulfilled with reliability of boiler greatly improved and good economic benefit obtained.
作者 李瑞群
机构地区 湖北汉川电厂
出处 《中国电力》 CSCD 北大核心 2001年第5期7-9,40,共4页 Electric Power
关键词 锅炉 泄漏 磨损 温度场 速度场 受热面 电厂 boiler leakage wear temperature field velocity field
  • 相关文献

参考文献5

  • 1曾汉才.引进型300MW机组贫煤锅炉燃烧器反切改造的研究[M].华中理工大学出版社,1995..
  • 2-.湖北汉川电厂2号炉燃烧调整试验报告[M].电力部热工研究院,湖北汉川电厂,1996..
  • 3-.汉川电厂2号炉大修前对流烟道流场测试报告[M].电力部热工研究院,湖北汉川电厂,1996..
  • 4-.汉川电厂2号炉大修后对流烟道流场测试报告[M].电力部热工研究院,湖北汉川电厂,1996..
  • 5-.汉川电厂2号炉尾部受热面防磨措施的模化试验研究[M].电力部热工研究院,湖北汉川电厂,1996..