期刊文献+

大尺寸四角切圆燃烧锅炉汽温偏差原因分析及措施 被引量:2

An Analysis of the Cause Leading to Steam Temperature Deviation in a Large-sized Tangentially Fired Boiler and Measures Taken for Its Alleviation
下载PDF
导出
摘要 通过对锅炉热力特性试验和热力计算的全面比较 ,并对其进行分析研究 ,把通常设计在后屏至末级的连接管由交叉形式改为平行方式 ,实际运行表明 :其改动是成功的 ,效果显著。 A comprehensive comparison was conducted of the results of the thermodynamic testing of a boiler with those of the boiler thermodynamic calculation followed by a pertinent analytic study. On this basis the pipe connecting a rear panel to the last row of a tube bank was changed from a cross-connected form to a parallel-connected one. Ensuing operation of the modified boiler indicates that such a modification has been highly successful.
出处 《热能动力工程》 EI CAS CSCD 北大核心 2001年第3期336-337,共2页 Journal of Engineering for Thermal Energy and Power
关键词 切圆燃烧锅炉 汽温偏差 热力特性 tangentially fired boiler, steam temperature deviation, cross connected pipe
  • 相关文献

参考文献1

二级参考文献2

共引文献3

同被引文献16

引证文献2

二级引证文献11

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;