摘要
用少量投资 ,改造老式 D 4.7m风机及砼塔内部构件 ,使塔内收水、配水、喷淋达到了最佳组合。改造后的冷却塔产生了较高的效率 ,单塔水处理能力由原 30 0 t/ h提高到了 5 0 0 t/ h,进出塔水温差由 5~ 7℃提高到了 8~
To make water collection,distribution and spray in the tower get the best assembling,they reconstructed the vintage 4.7 m exhaust fan and its inside components of concrete cooling tower with less investment. The reconstructed cooling tower can bring higher efficiency,the water disposal capacity of the single tower gets to 500 t/h from 300 t/h,inlet and outlet difference in water temperature gets to 8~9 ℃ from 5~7 ℃.
出处
《工业水处理》
CAS
CSCD
2001年第7期45-46,共2页
Industrial Water Treatment
关键词
砼塔内件
改造
冷却塔
水温差
通风机
水处理
inside component of concrete tower
reconstruction
difference in water temperature