再论三峡电站1号发电机内部故障主保护配置方案的研究 被引量:3

Reconsideration of the main protection scheme of internal faults for No.1 generator in the Three Gorges power station
下载PDF
导出
摘要 在对三峡电站 1号发电机所有可能发生的同槽和端部交叉故障进行仿真计算的基础上 ,对两套零序电流型横差保护、不完全裂相横差保护、两套不完全纵差保护的组合的灵敏性与两套零序电流型横差保护、传统裂相横差保护、两套不完全纵差保护的组合的灵敏性进行了对比和分析 ,在此基础上提出了 1号发电机内部故障主保护的总体配置方案。 Based on the simulation of all kinds of slot and end faults of No.1 generator in the Three Gorges Power Station, the paper analyzes the difference of sensitivity between the combination of two kinds of zero-sequence current transverse differential protection, incomplete split-phase transverse differential protection and two kinds of incomplete longitudinal differential protection and the combination of two kinds of zero-sequence current transverse differential protection, traditional (complete) split-phase transverse differential protection and two kinds of incomplete longitudinal differential protection. Then the main protection scheme of internal faults is proposed for No.1 generator in the Three Gorges Power Station.
出处 《继电器》 CSCD 北大核心 2001年第9期10-16,共7页 Relay
关键词 水轮发电机 内部故障 主保护 三峡电站 generator internal faults main protection schemes and their combination advantages complement traditional (complete) and incomplete split-phase transverse differential protection