摘要
通过对两起保护动作情况的分析 。
Based on the analysis of two transformer failures, it was found that the 'trip' circuit board of the relay system contained a design error. The 'trip' circuit board is powered by Direct Current from two sets of storage batteries. This paper discusses the cause of the failure and offers corrective action.
出处
《继电器》
CSCD
北大核心
2001年第9期72-73,共2页
Relay
关键词
变电站
直流系统
可靠性
蓄电池系统
寄生回路
main transformer
maloperation of protection
storage battery
sneak circuit