期刊文献+

南上座泵站最优补偿功率因数分析

Analysis of optimum compensation power factor about Nanshangzuo pump station
下载PDF
导出
摘要 从提高泵站运行效率的观点 ,结合宝鸡峡南上座泵站机组的实际资料 ,对该泵站异步电动机组进行补偿分析 ,找出了功率因数与无功补偿容量、投资变化率及投资回收年限之间的关系。结果表明 ,在南上座泵站 ,异步电动机组功率因数补偿到 0 .94时最为经济。 In view of raising the operational efficiency of the pump station and combined with the actual data of the units of Nanshangzuo pump station in Baojixia irrigated area,the compensating analysis is completed to the asynchronous motors of the pump station.The relations between power factor and reactive compensating capacity,investment change rate as well as investment payback period have been established,the result illustrates that the operation cost is the cheapest when power factor of the asynchronous motors is compensated and increased to 0.94.
出处 《西北农林科技大学学报(自然科学版)》 CSCD 北大核心 2001年第6期112-114,共3页 Journal of Northwest A&F University(Natural Science Edition)
基金 国家自然科学基金资助项目 ( 4 98710 40 )
关键词 异步电动机 功率因数 投资回收年限 无功补偿容量 投资变化率 南上座泵站 asynchronous motor power factor investment payback period economic benefit
  • 相关文献

参考文献8

  • 1张勖成 陈前明 等.给排水手册(第8册)[M].北京:中国建筑出版社,1986..
  • 2肖鸿猷 徐约珥 等.电工学基本教程[M].北京:高等教育出版社,1987..
  • 3航空工业部第四规划设计研究院 兵器工业部五院 等.工厂配电设计手册[M].北京:水利电力出版社,1987..
  • 4季一峰.水电站(电气部分)[M].北京:水利电力出版社,1985..
  • 5肖鸿猷,电工学基本教程,1987年
  • 6航空工业部第四规划设计研究院,工厂配电设计手册,1987年
  • 7张勖成,给排水手册.8,1986年
  • 8季一峰,水电站,1985年