天广交直流并联系统运行稳定性的研究 被引量:7

Study on Operation Stability for Tian-Guang AC /DC Hybrid System
下载PDF
导出
摘要 根据天广500kV直流输电工程投运初期南方电网的实际运行工况,对天广交直流输电系统并联运行的稳定性及输电能力进行分析研究。研究结果表明,天广直流输电工程投产后与天广交流双回输电线路并联运行,南方电网的稳定性明显提高。天广交直流系统在天生桥出口断面送电能力可达到3600MW。为保证系统的安全稳定运行,当直流线路发生单双极故障时需采取适当的稳定措施。同时,广西电网运行条件的变化对天广交直流输电系统安全稳定运行有明显影响,增强广西电网动态无功支持能力对提高天广交直流输电系统的送电能力有重要作用。 The stability and transmission ability of the parallel operation in Tianguang AC-DC hybrid system is analyzed,based on the actual operation conditions of the power system in the south China in the early period of operation of Tianguang500kV HVDC system.It is concluded in the study that the stability of the network is obviously improved because of the Tianguang HVDC project and its operation in parallel with Tianguang HVAC transmission lines,and the total transmission capability in Tianshengqiao can be raised to3600MW in the system.To assure the stability operation,it is necessary to take measures in the faults of the monopole and bi-pole in DC lines.Due to the evident effect of operation condition changes in Guangxi power system on stability operation of the system,To strengthen the dynamic reactive power capability in Guangxi network seems important to enhance the transmission ability of Tianguang AC-DC hybrid system.
出处 《中国电力》 CSCD 北大核心 2002年第1期46-49,共4页 Electric Power
关键词 交直流并联系统 运行稳定性 电网 电力系统 AC-DC hybrid system parallel operation transmission ability stability stability measure
  • 相关文献

参考文献3

  • 1国家电力公司南方公司 中国电力科学研究院.直流单极投运下天广交直流并联系统稳定及安全性能研究[M].,2000..
  • 2国家电力公司南方公司 中国电力科学研究院.直流双极投运下天广交直流并联系统稳定及安全性能研究[M].,2000..
  • 3南方电力调度通信中心.南方电网运行方式[M].,2001..

同被引文献17

引证文献7

二级引证文献22

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部