期刊文献+

CD-10型发电机差动保护误动作原因分析及对策

Cause Analysis of CD-10Generator Differential Protection Misoperation and Its Countermeasures
下载PDF
导出
摘要 根据故障录波图对穿越性故障电流进行了定量计算,对差动回路暂态不平衡电流、差动继电器最小动作电流、最小制动电流以及制动系数的实际整定配合进行了分析。结合事故后检查的差动继电器特性,分析说明了该保护误动的真正原因。提出了相应的对策。 According to the failure current oscillograph and quantitative calculation of exterior fanlt current.the tran-sient unbalance current of the differential circuit,the minimum operating current,the min imum restraint cur rent and the percentage restraint factor have been analyzed in this paper.Combined the checked characteristics of the CD-10defferential relay after its misoperation,the real cause of this differential pro tection misoperation and its countermea-sures are proposed.
机构地区 妈湾发电总厂
出处 《华中电力》 2001年第6期33-35,共3页 Central China Electric Power
关键词 发电机 差动保护 误动作 CD-10型 电力系统 Protection misoperation,transient unbalance current,the minimum restraint current,countermeasures.
  • 相关文献

参考文献2

  • 1王维检.发电机变压器继电保护整定算例[M].北京:中国电力出版社,2000,10..
  • 2王维检.电气主设备继电保护原理与应用[M].北京:中国电力出版社,1996,1..

共引文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部