期刊文献+

基于小波理论的局部放电超声波信号分析 被引量:3

Analysis of Partial Discharge Ultrasonic Signal Based on Wavelet
下载PDF
导出
摘要 变压器局部放电超声波信号在变压器内部中传播复杂 ,探头所接受到的超声波信号是一种时频有限的非平稳信号 ,所以运用小波分析处理超声波信号十分有效。通过实验得到处理超声波信号最合适的小波 ,同时给出合适的小波参数 ,最后对实际得到的超声波信号进行处理 。 Monitoring partial discharge is important for diagnosing insulation fault in transformers. Ultrasonic signal method is the main way to locate partial discharge in transformers, because transmitting modes of ultrasonic signal in transformers are very complicated. The ultrasonic signal is non smoothness signal with finite time frequency, so it is very effective to process ultrasonic signal utilizing wavelet conversion. The most ideal wavelet for analyzing ultrasonic signal and the way to select parameters of wavelets are presented. Finally, the actual ultrasonic signal in transformers model is processed. A conclusion can be drawn that the method of using wavelet analysis to process ultrasonic signal can improve the partial discharge location precision in transformers.
作者 谢红玲
出处 《电力情报》 2002年第1期30-31,43,共3页 Information on Electric Power
关键词 局部放电 超声波信号 小波分析 小波理论 电力变压器 信号分析 partial discharge ultrasonic signal wavelet analysis
  • 相关文献

参考文献5

二级参考文献5

共引文献60

同被引文献21

  • 1金显贺,朱德恒,谈克雄.电力变压器绝缘局部放电的声发射频谱[J].电工技术学报,1989,4(4):40-45. 被引量:6
  • 2张江,李朝晖,王宏.基于超声波法的变压器局部放电监测系统设计[J].湖北电力,2006,30(1):28-30. 被引量:5
  • 3郭艳平,解武波,郑小平.声发射技术及其在变压器局部放电检测中的应用[J].现代电子技术,2007,30(17):137-140. 被引量:5
  • 4Jest~s Rubio- Serrano, Ju|io Posada, Iago Bua, et al. Comparison of Processing Techniques for Optimizing the Diagnosis of Solid Insulation based on Acoustic Emissions from Partial Discharges [ C ]// 2013 IEEE International Conference on Solid Dielectrics. Bologna:IEEE,2013:129 - 132.
  • 5Prasanna Venkatesh A S, Danikas M G, Sarathi R. Under- standing of Partial Discharge Activity in Transformer Oil under Transient Voltages Adopting Acoustic Emission Technique[ C]//2011 6th International Conference on Industrial and Information Systems. Sri Lanka: IEEE, 2011:98 - 101.
  • 6Syed Aqeel Ashraf, Brian G Stewart, Chengke Zhou, et al. Modelling of Acoustic Signals from Partial Discharge Activity [ C ]//GCC Conference ( GCC ). Manama : IEEE, 2006 il -5.
  • 7Howells E,Norton E T. Detection of Partial Discharges in Transformers Using Acoustic Emission Technique [ J ]. IEEE Transactions on Power Apparatus and Systems, 1978, PAS - 97 (5) : 1538 - 1549.
  • 8Giscard F Cintra Veloso, Borges da Silva L E, Lambert- Torres G, et al. Localization of Partial Discharges in Transformers by the Analysis of the Acoustic Emission [C ]//IEEE ISIE 2006. Montreal: IEEE, 2006:537 - 541.
  • 9Du B X,Lu Y H ,Weil G Z ,et al. PD Localization Based on Fuzzy Theory using AE Detection Techniques [ C ]// 2005 Annual Report Conference on Electrical Insulation and Dielectric Phenomena. USA :IEEE ,2005:449-452.
  • 10Prasanta Kundu, Kishore N K, Sinha A K. Wavelet based Fractal Analyzing Method of Partial Discharge Acoustic Emission Signal[ C]// Second International Conference on Industrial and Information Systems. Sri Lanka:IEEE, 2007:357 - 360.