期刊文献+

电厂辅机变频器柜运行可靠性提升方案的研究 被引量:1

Operation Reliability Improvement Scheme for Power Plant Auxiliary Machine Frequency Converter Cabinet
下载PDF
导出
摘要 引发火力发电厂辅机变频器运行异常最主要的原因是变频器直流母线滤波电容老化与屏柜散热不良,提出了一种提升变频器的运行可靠性的方案,阐述了对屏柜散热技术、变频器直流母线部分的改进措施,对改进方案进行了验证,可有效地提高辅机变频器柜的工作可靠性,降低因辅机设备异常停机导致的跳闸概率。 It has been pointed that many tripping accidents caused by faults in auxiliary power plants are related to abnormal operation of inverters.The most important cause of these serious abnormalities is inverter DC bus filtering.or the heat dissipation of the panel is poor.Aiming at the above problems,a series of new schemes and ideas are proposed.The preliminary practice proves that it can effectively improve the operational reliability of the auxiliary inverter cabinet and reduce the trip probability caused by the abnormal shutdown of the auxiliary equipment.
作者 肖峰 朱涛 杨欢红 刘新超 李广一 朱伟星 XIAO Feng;ZHU Tao;YANG Huanhong;LIU Xinchao;LI Guangyi;ZHU Weixing(Shanghai Fengxian Gas Turbine Power Generation Co.,Ltd.,Shanghai 201499,China;School of Electrical Engineering,Shanghai University of Electirc Power,Shanghai 200090,China)
出处 《电力与能源》 2018年第6期884-888,共5页 Power & Energy
关键词 火力发电厂 变频器柜 直流母线 滤波电容 散热 纹波 thermal power plant frequency converter cabinet DC bus filter capacitance heat dissipation ripple
  • 相关文献

参考文献10

二级参考文献35

共引文献39

引证文献1

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部