摘要
分析了一起110kV变压器绝缘下降的原因。通过对变压器油的化验结果分析,并与类似故障的统计比较,发现油中铜离子含量偏高是变压器绝缘下降的根本原因。针对分析结果 ,提出了处理措施,试验结果验证了处理措施的有效性。
The reason of 110kV transformer's insulation deterioration is analysised in this paper.The transformer's oil is tested and analogy fault is compared,then the reason of insulation deterioration-copper ion bigger is discovered.The ameliorate way has been proposed also and the analysis'correctness is validated on test result.
作者
杨伟超
董家读
张峰
YANG Wei-chao;DONG Jia-du;ZHANG Feng(Foshan Power Supply Bureau,Foshan 528000 China)
出处
《自动化技术与应用》
2019年第1期121-123,共3页
Techniques of Automation and Applications
关键词
变压器油
绝缘下降
铜离子
transformer oil
insulation resistance
copper ion