CFG桩复合地基的试验研究 被引量:34

Experimental Study on CFG Pile Composite Foundation
原文传递
导出
摘要 本文介绍了一个CFG桩加固软土地基的工程实例。结合该工程,对CFG桩复合地基的设计方法进行了简要阐述;采用有限元ANSYS程序对CFG桩复合地基的应力传递特性进行了分析;对CFG桩体的强度和弹性模量进行了测试,对CFG桩体、CFG桩复合地基进行了静载荷试验,对桩间土进行了标准贯入试验。试验和分析结果表明:CFG桩能够把荷载传递到深层土上;CFG桩复合地基与天然地基的变形比随面积置换率m的增大而减小,且当m<10%时,效果显著;经CFG桩处理后的复合地基的承载力高达天然地基承载力的2.5倍以上,打桩过程的振动作用和挤密作用可以消除或降低桩间土的液化。 This paper presents a real engineering project by using cement flyash gra vel(CFG)pile for reinforcing soft foundation in north China.In combin ation with the project,the design me thod of CFG pile composite foundatio n has been expounded briefly.The characteristics of loading transmission of the CFG pile composite foundation has been an-alyzed by use of the ANSYS program.The cubic strength and elastic modulus of CFG mixture have been tested and th e site loading tests of CFG pile and CFG pile composite foundation together with the standard penetration test o f soil be-tween piles have been performed.The results of tests and analysis indicate that CFG pile can transfer the load ing into deep soil,the higher the replacing r atio m,the smaller the deformation ratio,and when m<10%,increasing m will effectively result in decreasing th e deformation of composite foundati on while the bearing capacity of CFG p ile composite foundation can be over 2.5times more than that of natural soil.Furthermo re,the vibration and compaction eff ects during pile driving may eliminate liquefac tion of the soil between piles.
出处 《建筑结构学报》 EI CAS CSCD 北大核心 2002年第4期71-74,84,共5页 Journal of Building Structures
关键词 试验 CFG桩 复合地基 静载荷试验 有限元分析 CFG pile,composite foundation,sta tic loading test,finite element analysis
  • 相关文献

参考文献1

  • 1闫明礼 张东刚.CFG桩复合地基技术及工程实践[M].北京:中国水利水电出版社,2001.49-51.

共引文献13

同被引文献198

引证文献34

二级引证文献142

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部