10kV配电变压器分接开关故障分析及防范措施 被引量:3

Fault Analysis and Preventive Measures of 10 kV Distribution Transformer Tap-Switch
下载PDF
导出
摘要 通过对一起配电变压器送电不成功事件进行了故障原因分析,确定故障原因是无励磁分接开关切换手柄被人为"反向",分接开关动静触头间出现悬浮电位,最终发展成相间弧光短路故障。针对配电变压器分接开关在实际使用中出现的隐患,提出了防范措施。 Through analyzed the reasons of an unsuccessful power transmission event,and determined the reason of the failure was that tap-switch handle was artificially 'reverse',floating potential appeared between static and dynamic contact of tap—switch,and eventually developed into the arc short-circuit fault.To solve the problem for hidden dangers which appeared in the actual use of distribution transformer tap-switch,put forward preventive measures.
作者 陶明杰
出处 《安徽电力》 2015年第2期4-5,共2页 Anhui Electric Power
关键词 配电变压器 无励磁条形分接开关 中部调压 切换手柄 空档 悬浮放电 distribution transformer no-load bar tap-switch central regulating switch handle neutral position suspended discharge