摘要
调查了上海地区12个单位有中央空调的视屏显示终端室内的职业环境。结果为气温16.5~24℃,相对湿度39~71%,风速0.02~0.3m/s,空气中CO_2浓度900~2052mg/m^3,细菌总数300~4500个/m^3,臭氧浓度0~2.5ppb。询问了71名工作人员主观感觉均有不适感。提示被调查的视屏显示终端室的空调环境空气不洁,臭氧浓度偏低;均有待改进。
Occupational environment in 12 VDT workrooms with central air conditioner was investigated in Shanghai. The results were as follows: the temperature was between 16.5~ 24℃, the relative humidity was 39~71%, the wind speed was 0.02~0.3m/s, the CO_2 concentration in air was 900~2052mg/m^3, the total bacteria counts was 300~4500 per kilolitre, the O_3 concentration in air was 0~0.005 mg/m^3, all of the 71 staffs felt uncomfortable in VDT workroom. It suggested that since the environment in those 12 VDT workrooms was dirty, and O_3 concentration in air was low, improvement was needed.
出处
《职业医学》
1991年第2期81-82,128,共2页
China Occupational Medicine