摘要 针对目前宁夏电网存在甘-宁断面多回联络线停电检修的现状,通过对甘-宁断面三回联络线进行停电方式下系统的热稳定、静态稳定、暂态稳定、动态稳定和小干扰稳定仿真计算分析,确定甘-宁断面在薄弱方式下对系统的稳定性影响。结果表明:甘-宁断面在多回联络线停电检修方式下对系统的稳定性影响较大,需对甘-宁断面采取预控措施,防止热稳定和动态稳定问题的发生。 Ningxia Power Grid currently exists the status quo of Gansu-Ningxia section multiple loop interconnector outage maintenance,by simulation and calculation analysis on system's thermal stability,static stability,transient stability,dynamic stability and little interference stability under the mode of Gansu-Ningxia section triple loop interconnector outage, confirms the stability influence of Gansu-Ningxia section on system under weak mode. The result shows that Gansu-Ningxia section has larger influence on system stability under the mode of multiple loop interconnector outage maintenance,needs to take prevention measures for Gansu-Ningxia section,prevents the problem of thermal stability and dynamic statility to occur.
出处 《宁夏电力》 2014年第3期5-8,共4页 Ningxia Electric Power
关键词 甘-宁断面 静态稳定 暂态稳定 动态稳定 Gansu-Ningxia section static stability transient stability dynamic stability