摘要
The DRM (dynamic contact resistance measurement) in high voltage circuit breakers is a manner of evaluating the internal ageing condition of the chamber. DRM is similar to static contact resistance measurement testing, but instead of measuring a single value when the breaker contacts are closed (static value), the ohmic resistance is measured at various contact positions, from the beginning of the contact opening until a complete separation of the contacts. The relationship between the contact resistances of the new circuit breaker and the ageing circuit breaker in operation provides subsidy for the evaluation of both the main and arcing contact conditions. This research aims to analyze the correlation between the various levels of degradation of the contacts and the configuration of the DRM curve. This work considers curve samples from new acceleration tests. breaker chamber contacts and different levels of degradation by