正压送风-气幕联合防烟系统数值模拟 被引量:1

Numerical study on united smoke-prevention system of pressurization air supply and air curtain
下载PDF
导出
摘要 提出了正压送风-气幕联合防烟系统,以提高防烟楼梯间的防烟效果,减少系统总送风量。利用FDS模拟研究了气幕送风速率、送风角度对联合防烟系统总送风量的影响规律。结果表明,气幕的最佳设置参数为送风速率7m/s,气幕送风口向烟气区偏转25°;在最佳气幕设置参数下,当开启门数量为两扇时,联合防烟系统的总送风量为独立正压送风防烟系统送风量的50%~60%;在相同的有效送风量下,应用联合防烟系统进行楼梯间防烟时,可开启疏散门数量为应用正压送风防烟系统时的3~4倍。 A united smoke prevention system of pressurization air supply and air curtain was put forward,to improve the smoke prevention effectiveness and reduce the total air supply volume.By FDS,the effect of air curtain outlet rate and jet angle on the total air supply volume were studied.The results show that the optimal air curtain outlet rate is 7m/s,and the optimal jet angle is 25° leaning to the smoke area.With the optimal outlet rate and angle of air curtain,the total air supply volume rate of united system will reduce to 50%~60% compare with single positive pressure mechanical air supply system when 2 doors are opened.With the same total air supply,the opened door number using united system could be 3~4 times to using single positive pressure mechanical air supply system.
出处 《消防科学与技术》 CAS 北大核心 2013年第6期606-609,共4页 Fire Science and Technology
关键词 正压送风 气幕 联合防烟系统 FDS pressurization air supply system air curtain united smoke-prevention system FDS
  • 相关文献

参考文献4

二级参考文献7

  • 1巴图林BB 刘永年(译).工业通风原理[M].北京:中国工业出版社,1965.286-288.
  • 2He Jiapeng,Trans Nanjing Univ Aeronaut Astronaut,1997年,14卷,1期,77页
  • 3陈维,高层建筑火灾和防火安全,1986年,277页
  • 4孙一坚,工业通风,1985年,118页
  • 5安中义(译),建筑防烟排烟设备,1983年,45页
  • 6魏润柏,通风工程空气流动理论,1981年,95页
  • 7刘永年(译),工业通风原理,1965年,286页

共引文献92

同被引文献6

引证文献1

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部