摘要
介绍了秦山第二核电厂安全壳泄漏率在线监测系统(EPP系统)的应用。当安全壳泄漏率达到运行限值时,系统自动报警,及时通知机组操纵员采取必要的行动。使用过程中发现,EPP系统会偶尔出现"安全壳泄漏率异常"的非真实报警,该虚假报警对机组的正常运行会造成影响。分析了虚假报警的原因并指出,EPP系统的监测数据具有一定的延迟性,安全壳的压空注入流量的准确性对EPP系统的监测数据有很大影响。
The use of online monitoring system of containment leak rate(EPP) in Qinshan 2nd nuclear power plant is introduced. When the containment leak rate reaches the operational limit,the system will automatically alarm and inform the unit operator to take the necessary action. But it is found that the EPP will give a mendacious alarm of"Containment leak rate abnormity"once in a while during use. The mendacious alarm has an effect on the normal operation of the unit. The reason of the mendacious alarm is analyzed. The data monitored by the EPP are relative hysteretic and the veracity of the flow of compressed air into the containment has a significant influence on the data monitored by the EPP.
出处
《核安全》
2014年第2期56-60,55,共6页
Nuclear Safety
关键词
安全壳泄漏率监测
虚假报警
数据分析
containment leak rate testing
mendacious alarm
data analysis