期刊文献+

配网高阻接地故障伏安特性分析及检测 被引量:69

Analysis and Detection of Volt-ampere Characteristics for High Impedance Faults in Distribution Systems
下载PDF
导出
摘要 中性点有效接地中压配电网常发生弧光高阻接地故障,短路电流小,零序保护无法动作切除,但存在的电弧易引发火灾、人身伤亡等恶性事故。传统故障检测算法一般基于电弧热平衡模型,采用基于傅里叶变换的频域信号分析方法,但在非线性电弧的强噪声环境下检测成功率较低。针对该问题,首先提出了基于固体介质电击穿原理的非线性电弧模型,分析了电路线性元件和高阻接地非线性电阻的伏安特性,从时域角度采用最小二乘线性拟合抽取故障特征,提出了基于故障电阻非线性识别的高阻接地故障检测算法。大量仿真数据和现场试验数据证明了该故障模型比传统模型更精确,且所提检测算法具有较高的灵敏性和可靠性。 High impedance faults (HIFs) often occur in effectively grounded medium voltage (MV) distribution systems, while their fault currents are too low to be tripped by zero-sequence over-current protection, but the existing arc flash is easy to produce fire hazard and personal injury. Existing HIF detection (HIFD) algorithms, which are mainly based on arc thermal equation and frequency domain analysis based on Fourier transform, however, have a relatively poorer performance because of strong noises accompanied by arc flash Aiming to solve this problem, an accurate nonlinear resistance model, based on the solid dielectric electrical break-down theory, was proposed to simulate the fault point. After analyzing the Voltage-Current characteristics of linear electrical components and nonlinear arc resistance, a nonlinear resistance identification based HIFD algorithm was proposed with fault characteristic extraction by least square fitting. Extensive field data and simulation results testified the higher accuracy of the proposed fault model over traditional models, as well as high sensitivity and reliability of the proposed algorithm.
出处 《中国电机工程学报》 EI CSCD 北大核心 2014年第22期3815-3823,共9页 Proceedings of the CSEE
基金 国家自然科学基金项目(50937003 51007045 51120175001)~~
关键词 配电系统 高阻接地故障 伏安特性 最小二乘拟合 非线性识别 distribution systems high impedance faults volt-ampere characteristics least square fitting nonlinearidentification
  • 相关文献

参考文献21

  • 1董振亚.城市配电网中性点接地方式的发展和改进[J].中国电力,1998,31(8):38-41. 被引量:64
  • 2许庆强,许扬,周栋骥,奚雪峰.小电阻接地配电网线路保护单相高阻接地分析[J].电力系统自动化,2010,34(9):91-94. 被引量:65
  • 3Benner C L,Russell B D.Practical high-impedance fault detection on distribution feeders[J].IEEE Transactions on Industry Applications,1997,33(3):635-640.
  • 4崔韬.配电线路高阻接地故障检测技术的研究[D].北京:清华大学,2009.
  • 5PSRC Working Group D15.High impedance fault detection technology[R].USA:IEEE,1996.
  • 6Russell B D,Aucoin B M.Randomness fault detection system[P].U.S. Patent,5,485,093,Jan.16,1996.
  • 7Sultan A F,Swift G W,Fedirchuk D J.Detection arcing downed-wires using fault current flicker and half-cycle asymmetry[J].IEEE Transactions on Power Delivery,1994,9(1):461-470.
  • 8Jeerings D I,Linders J R.Unique aspects of distribution system harmonics due to high impedance ground faults [J].IEEE Transactions on Power Delivery,1990,5(2):1086-1094.
  • 9Jeerings D I,Linders J R.Ground resistance-revisited [J].IEEE Transactions on Power Delivery,1989,4(2):949-953.
  • 10Michalik M,Rebizant W.High-impedance fault detection in distribution networks with use of wavelet-based algorithm[J].IEEE Transactions on Power Delivery,1989,21(4):1793-1802.

二级参考文献20

共引文献125

同被引文献594

引证文献69

二级引证文献585

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部