摘要
介绍了3起基于气态分解产物测试和局部放电测试发现的典型SF6全封闭组合电器(GIS)内部潜伏性故障案例。这些案例各有特点:能检出气态分解产物但未检出局部放电信号;未检出气态分解产物但检出局部放电信号;检出气态分解产物的同时也检出局部放电信号。通过解体检查,均验证了设备存在缺陷。因此,气态分解产物和局部放电测试技术在GIS潜伏性故障诊断方面具有广阔的应用前景。
Based on gaseous DPD (decomposition products detection) and PD (partial discharge) detection,three typical cases of internal latent fault cases of GIS are introduced,which have different characteristics:the gaseous DPD result is abnormal but the PD signal is not detected; the gaseous DPD result is normal but the PD signal is detected; the gaseous DPD resuh is abnormal and the PD signal is detected.The equipment are verified to have defects through disintegration examination.Therefore,gaseous DPD and PD detection technologies have expectable application prospect in the internal latent fault detecting of GIS.
出处
《中国电力》
CSCD
北大核心
2014年第7期86-90,共5页
Electric Power
关键词
GIS
内部潜伏性故障
气态分解产物测试
局部放电测试
GIS
internal latent fault
gaseous decomposition products detection
partial discharge detection