分体式空调器长连接管制冷剂追加量的试验研究 被引量:2

Experimental research on additional refrigerant mass for long connecting pipe of split air-conditioner
下载PDF
导出
摘要 基于制冷量为12 kW的风管送风式空调(热泵)机组进行试验研究,分析节流位置、工况等因素对长连接管制冷剂追加量的影响,得出9.52 mm液管和15.88 mm气管条件下R410A制冷剂追加量的参考值。研究发现,对于单冷型空调器,节流位置会对长连接管的制冷剂追加量产生较大影响,室内机节流时的追加量大于室外机节流;而对于热泵型空调器,节流位置对长连接管制冷剂追加量的影响较小。 The experimental research is conducted based on a ducted air-conditioning(heat pump)unit of 12 kW cooling capability.The influences of the location of throttle device and operating condition on the amount of additional refrigerant mass of long connecting pipe are analyzed.The amount of additional mass of R410 A refrigerant is recommended when the liquid connecting pipe is9.52 mm and the gas connecting pipe is15.88 mm.The study results show that for the cooling-only unit,the additional mass is highly dependent on the location of throttle device.More additional refrigerant is required when the throttle device is installed close to the indoor unit than it is close to the outdoor unit.For the heat pump unit,the throttle device's location doesn't have large effect on the additional refrigerant amount of long connecting pipe.
作者 王磊
出处 《制冷与空调》 2014年第8期67-70,共4页 Refrigeration and Air-Conditioning
关键词 空调器 长连接管 制冷剂追加量 节流位置 air-conditioner long connecting pipe additional refrigerant mass location of throttle device
  • 相关文献

参考文献3

  • 1杨恒辉,徐亮,丛丽.提高轻型商用空调长配管性能的实验探讨[C]//第八届全国空调器、电冰箱(柜)和压缩机学术交流会.珠海.2006.9.
  • 2苏顺玉,张春枝,陈俭.空气源热泵毛细管节流空调系统的研究[J].湖南大学学报(自然科学版),2009,36(S2):1-3. 被引量:7
  • 3中国国家标准化管理委员会.GB/T 7725-2004 房间空气调节器[S],2004

二级参考文献8

  • 1饶荣水,周泽,申建军,肖建军,谷波.采用R134a和R600a制冷剂系统毛细管特性分析[J].制冷与空调,2005,5(1):70-74. 被引量:4
  • 2Bansal P K,Rupasinghe A S.An homogeneous model for adiabatic capillary tubes. Applied Thermal Engineering . 1998
  • 3Wang H,Touber S.Distributed and non-steady-state modeling of an air cooler. International Journal of Refrigeration . 1991
  • 4Wongwises S,Songentichavalit T,Lokathada N,et al.A comparison of the flow characteristics of refrigerants flowing through adiabatic capillary tubes. International Communications in Heat and Mass Transfer . 2000
  • 5Shah M M.A general correlation for heat transfer during film condensation inside pipes. International Journal of Heat and Mass Transfer . 1979
  • 6Todd M. Harms Daqing Li,Eckhard A. Groll and James E. Braun.A void fraction model for annular flow in horizontal tubes. International Journal of Heat and Mass Transfer . 2003
  • 7苏顺玉,张春枝,陈俭.热泵型空调系统制冷剂流量控制方法的研究[J].暖通空调,2009,39(3):128-130. 被引量:8
  • 8高原,田怀璋,曾艳,袁秀玲.用数值方法分析绝热毛细管的流量特性[J].流体机械,2002,30(7):47-49. 被引量:7

共引文献43

同被引文献4

引证文献2

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部