期刊文献+

高压放电紫外检测系统及故障定位的研究 被引量:4

Ultraviolet-based Detection System and Fault Location for High-voltage Discharge
下载PDF
导出
摘要 针对高压设备电晕放电和故障点定位的问题,设计了一种基于紫外电晕技术的高压放电检测系统,介绍了系统的主要设备及功能。同时,研究出一套基于滤光片切换的单通道滤光成像法,通过该套方法可使紫外与可见光两种光谱分别经过系统光路,完成最后的图像采集与融合,在单通道光路结构下达到电晕定位的目的。通过成像实验,证明该方法的可行性。 Aiming at corona discharge and fault location in high-voltage apparatus,a high-voltage discharge detection system based on ultraviolet(UV)corona technology was designed. The main devices in the system and their functions are introduced in this paper. Moreover,a single-channel imaging method based on filter switching was proposed, in which UV spectrum and visible light spectrum individually go through the system's optical tunnel to complete the final image acquisition and fusion, so as to achieve corona location via the single-channel optical structure. Imaging experiment shows the feasibility of the present high-voltage discharge detection system and single-channel imaging method.
出处 《高压电器》 CAS CSCD 北大核心 2014年第9期12-15,22,共5页 High Voltage Apparatus
基金 国家自然科学基金(61205076) 上海市研究生创新基金项目(JWCXSL1302)~~
关键词 高压设备 电晕放电 紫外 定位 high-voltage apparatus corona discharge UV location
  • 相关文献

参考文献21

二级参考文献129

共引文献283

同被引文献46

  • 1张海峰,庞其昌,李洪,张工力.基于UV光谱技术的高压电晕放电检测[J].光子学报,2006,35(8):1162-1166. 被引量:38
  • 2刘云鹏,马国明,刘肇鸥,律方成,杨晓琳.低通滤波在紫外成像降噪处理中的应用[J].高电压技术,2007,33(6):129-132. 被引量:7
  • 3MARKUS D T, LEE T S, A method of direct corona imaging on a dielectric transparency[J]. IEEE Trans. Ind. Appl., 1996,32(4): 832-836.
  • 4ARAO Y,FUJII T,YATSUZUKA M. Image evaluation of atmospheric corona discharge applied for road tunnel high- velocity electrostatic precipitator[J]. IEEE Trans. on Plas-ma Sci.,2005, 33(2): 312-313.
  • 5CARDOSO J A, FILHO O, LEVY A F. Correlating digital measurements of electrical quantifies and related images on micro discharges under high voltages[C]//2008 Interna- tional Conference on High Voltage Engineering and Ap- plication. Chongqing, China: IEEE, 2008 : 9-13.
  • 6WATSON D B, KHO S K, SAMUEI.,S K A, et al. Impulse flashover trajectory in air in non-uniform fields[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 1993,28(2): 200-208.
  • 7QIU D H, MACALPINE J M, LI Z Y. An incremental analysis of spark paths in air using 3-dimensional image processing[J]. IEEE Transactions on Dielectrics and Elec- trical Insulation, 2000,7(6) : 758-763.
  • 8WEI Gang, TANG Ju. Study of minimum box-counting method for image fractal dimension estimation [C]//2008 China International Conference on Electricity Distribution, (CICED). Guangzhou, China: IEEE, 2008 : 1-5.
  • 9AMARASINGHE D, SONNADARA U,BERG M,et al. Correlation between brightness and channel currents of electrical discharges[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2007,14(5): 1154-1160.
  • 10WU Y,YE Q,LI X. et al. Classification of dielectric barrier discharges using digital image processing technology[J]. IEEE Transactions on Plasma Science, 2012,40 (5) : 1371- 1379.