期刊文献+

火灾下铝合金方管柱的升温 被引量:4

Temperature rises of square aluminium alloy tubular columns in fire
下载PDF
导出
摘要 采用有限元法计算了无保护层和带防火保护层铝合金方管柱在火灾下的温度场,并将计算结果与Eurocode 9升温公式以及实验结果进行比较,考察了截面形状系数、保护层厚度与导热系数比的影响规律。研究结果表明,对于无防火保护的构件,辐射安全系数为1时Eurocode 9预测结果太高,而安全系数0.15的计算结果与实测值和有限元值吻合良好,对于防火保护的构件,Eurocode 9的计算结果和有限元结果非常接近。随着截面形状系数的增加或保护层厚度与导热系数比的减小,相同时间下铝合金方管柱的平均温度越高。 Temperature fields of unprotected and protected square aluminium alloy tubular columns in fire were calculated by finite element method.The calculated temperature results were compared with the results according to the temperature rising formulae in Eurocode 9 and experiment results.The influences of section shape factor and ratio of fire board thickness to thermal conductivity were investigated.The research results showed that,the predicted results of Eurocode 9 are too high when the safety coefficient due to radiation is taken as 1 for unprotected members.When the coefficient is taken as 0.15,the predicted results agree well with the test results and finite element results.As for protected members,the comparison of predicted results of Eurocode 9 and finite element method is quite good.With the increase of section shape factor or reduce of the ratio of fire board thickness to thermal conductivity,the average temperatures of square aluminium alloy tubular columns increase at the same fire duration time.
出处 《消防科学与技术》 CAS 北大核心 2014年第9期991-994,共4页 Fire Science and Technology
基金 国家自然科学基金项目"铝合金结构构件滞回性能研究"(51208109) 福建省自然科学基金项目"火灾下型钢混凝土柱-钢筋混凝土梁节点的工作机理研究"(2012J05083)
关键词 铝合金方管柱 温度场 有限元 aluminium alloy square tubular column temperature field finite element
  • 相关文献

参考文献16

  • 1Maljaars J.Literature study on aluminium structures exposed to fire[R] .Netherlands Institute for Metals Research,Technical University of Eindhoven,TNO Built Environment and Geosciences,2005.
  • 2Langhelle N K,Eberg E,Amdahl J.A comparative study between numerical models and buckling tests of aluminium columns at elevated temperatures[C] .Offshore Mechanics and Arctic Engineering Conference,OMAE' 98,Lisboa,1998.
  • 3Langhelle N K,Amdahl J.Experimental and numerical analysis of aluminium columns subjected to fire[C] //Proceedings of the Eleventh International Offshore and Polar Engineering Conference.Stavanger,2001.
  • 4Maljaars J,Soetens F,Snijder H H.Local buckling of aluminium structures exposed to fire.Part1:Tests[J] .Thin-Walled Structures,2009,47:1404-1417.
  • 5Maljaars J,Soetens F,Snijder H H.Local buckling of aluminium structures exposed to fire.Part 2:Finite element models[J] .Thin-Walled Structures,2009,47:1418-1428.
  • 6Maljaars J,Soetens F,Snijder H H.Local buckling of fire-exposed aluminum members:New design model[J] .Journal of Structural Engineering,ASCE,2010,136(1):66-75.
  • 7Maljaars J,Twilt L,Soetens F.Flexural buckling of fire exposed aluminium columns[J] .Fire Safety Journal,2009,44 (5):711-717.
  • 8Suzuki J,Ohmiya Y,Wakamatsu T,et al.Evaluation of fire resistance of aluminum alloy members[J] .Fire Science and Technorogy,2005,24(4):237-255.
  • 9BS EN 1999 1-2:2007,Eurocode 9-Design of aluminium structures-Part 1-2:Structural fire design[S] .
  • 10Li G Q,Wang P J.Advanced analysis and design for fire safety of steel structures[M] .Hangzhou:Zhejiang University Press,and Heidelberg:Springer-Verlag Berlin,2013.

二级参考文献14

  • 1李国强,杜咏.大空间建筑顶部火灾空气升温的参数分析[J].消防科学与技术,2005,24(1):19-22. 被引量:19
  • 2李国强,杜咏.实用大空间建筑火灾空气升温经验公式[J].消防科学与技术,2005,24(3):283-287. 被引量:74
  • 3褚新颖,屈立军,张少民.火灾中受保护钢构件的温度数值计算[J].消防科学与技术,2007,26(1):38-39. 被引量:3
  • 4CECS200:2006,建筑钢结构防火技术规范[s].北京:中国计划出版社,2006.
  • 5屈立军.建筑结构性能化耐火设计[M].廊坊:中国人民武装警察部队学院出版社,2004.
  • 6中国工程建设标准化协会.CECS200-2006,建筑钢结构防火技术规范[s].2006:9-10.
  • 7王秀丽.大跨度空间钢结构分析与概念设计[M].北京:机械工业出版社出舨.
  • 8Andrew H Buchanan. Structural Design for Fire Safety[M],2001 : 179.
  • 9J10041-2000,建筑钢结构防火技术规程[S].
  • 10李国强,蒋首超,林桂祥.钢结构抗火计算与设计[M].北京:中国建筑工业出版社,1998.

共引文献20

同被引文献83

引证文献4

二级引证文献6

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部