摘要
某电厂S109FA机组在运行过程中,突然出现机组除盐水补水量增大的异常现象,采用运行技术手段对机组除盐水补水量异常增大的分析判断,利用质量守恒定律分析,得出余热锅炉低压系统泄漏。结合同类型电厂的调研对比及广东电网公司电力科学研究院的分析,得出流动加速腐蚀是造成低压蒸发器泄漏的原因。根据机组的实际运行情况提出相应的解决方案,保证了机组的安全、经济运行。
With the help of operational and technological means , this essay introduces the analytic judgment of the abnormal augmentation of the amount of the desalted water supplement of the S 109FA unit in a power plant during its operation .Relevant analysis based on the law of conservation of mass reveals the leakage of the low -voltage sys-tem of the exhaust-heat boiler .The surveys in power plants of the same type together with the analysis performed by Electric Power Research Institute of Guangdong Power Grid Corporation show that the leakage of the low -pressure e-vaporimeter is caused by the flow accelerated corrosion .According to the operation of the unit ,this essay puts for-ward relevant solutions to ensure its safe and economical operation .
出处
《重庆电力高等专科学校学报》
2014年第4期45-49,共5页
Journal of Chongqing Electric Power College
关键词
除盐水
低压蒸发器泄漏
流动加速腐蚀
分析与处理
desalted water
leakage of the low-pressure evaporimeter
flow accelerated corrosion
analysis and treat-ment