摘要
通过对某站220 kV主变无载分接开关解体检修,发现分接开关三相动、静触头上有不同程度的黑色碳化点,判断为产生乙炔的主要原因,经返厂大修合格。
Through the a 220 kV main transformer no-load tap switch overhaul, the different levels of black carbon in tap switch three phase dynamic and static contact were found, which was the primary reason for generating acetylene. After repairing, equipment became qualified.
出处
《贵州电力技术》
2014年第10期61-62,共2页
Guizhou Electric Power Technology
关键词
主变
无载分接开关
动
静触头
main transformer
no-load tap switch
moving contact and fixed contact