期刊文献+

蒙东地区变压器直流偏磁现象检测与抑制方法

Detection and Suppression Method of DC Magnetic Bias on Transformers
下载PDF
导出
摘要 直流偏磁是影响变压器正常工作运行的一种典型现象。在分析变压器直流偏磁产生机理的基础上,认为直流输电系统入地电流是产生直流偏磁的主要影响因子。采用开发的直流偏磁带电测试仪和直流偏磁在线监测系统对蒙东地区的变压器中性点直流分量进行了测试。结果表明,蒙东地区变压器中性点直流分量已影响变压器的正常运行。 DC magnetic bias could affect the normal operation of the transformer,which is a typical phenomenon on transformer failure. Analyzed the mechanism of DC bias current on transformer,the ground current from adjacent DC power lines is the main factors.Adopt the Detection instrument of DC magnetic bias and Online monitoring system of DC magnetic bias,the DC component on neutral point of transformers are detected.The results show that DC coraponent is generally not more than 10A of Mengdong transformers,hut in this case, the normal operation of the transformer has been impact.
出处 《科技创新导报》 2014年第22期63-66,共4页 Science and Technology Innovation Herald
关键词 变压器 直流偏磁 中性点电流 带电检测 在线监测 蒙东地区 影响 Transformer DC Magnetic bias Neutral current Living detection Online monitoring Mengdong District impact
  • 相关文献

参考文献7

  • 1刘振亚.特高压电网[M].北京:中国经济出版社,2006.
  • 2梅桂华,梁文进,刘艳村,孙元章,王丹,毛承雄.变压器直流偏磁电流阻容抑制装置的开发应用[J].高电压技术,2009,35(10):2581-2585. 被引量:52
  • 3P. P i c h e r,L . B o 1 d u c ’ V _ O. P h a m .Study of the acceptable D Ccurrent limit in core-from powertransforrners[J].IEEE Transactionson Power Delivery,1997,12(1):257-263.
  • 4蒋伟,黄震,胡灿,朱康,吴广宁,周力任,任志超.变压器接小电阻抑制直流偏磁的网络优化配置[J].中国电机工程学报,2009,29(16):89-94. 被引量:33
  • 5A. P. Sakis, Meliopou los, Elias N.Glytsis. Comparison of SS- GIC and MHD-EMP-GIC effects on power systems[J].IEEE Transactions on Power Delivery, 1994,9(1):194-207.
  • 6Ram sis S.Girgis, Chung-DuckKo.Calculation techniques andresults of effects of GIC currentsas applied to two large powertransformcrs[J].IEEE Trans.onPower Delivery, 1992,7(2) :699-705.
  • 7浙江省电力公司.油浚试变座器(电抗器)状态评价导则[S].Q/GDW -11-106-2010,2010.

二级参考文献33

共引文献108