部分热回收风冷热泵冷热水机组性能实验研究

Experimental Research on Performance of Partial Heat Recovery Air-cooled Heat Pump Water Chiller-heater Units
下载PDF
导出
摘要 以一台额定制冷(热)量为45kW的部分热回收风冷热泵机组为平台,研究和分析了样机在名义制冷、名义制热工况,在保持使用侧和热回收侧水流量不变条件下,开启热回收功能后得到出水温度为45℃和50℃热水时样机的运行参数和性能变化规律。结果表明,在名义制冷工况45℃和50℃热水出水温度时,样机制冷性能系数(COP)比无热回收分别变化-10.55%-1.09%和3.64%-12.73%,热回收综合制冷COP分别达到3.38-3.69和2.98-3.15,出水温度由45℃升高到50℃且分别采用单双风机冷凝时,样机制冷COP下降2.44%-4.68%;在名义制热工况热水45℃和50℃出水温度时,样机制热COP比无热回收降低10.96%-21.58%,50℃出水时制热COP比45℃出水时升高4.42%,热回收综合制热COP分别达到了3.28和3.09。 Experimental researches are carried out on the performance of air-cooled heat pump water chillerheater module units with partial heat reclamation system whose rated refrigerating or heating amount is 45 kW. These experiments are realized on the prototype under the condition of nominal heating condition and nominal cooling condition. During the testing, the water flow rates of the used side and the heat recovery side of two kinds of working condition are fixed, and the variance characteristics of operating parameters and system performance are studied and analyzed after opening heat recovery function of the prototype under the two kinds of working condition getting the hot water of 45 ℃ and 50 ℃respectively. Comparing with no heat recovery situation, the results shows that the refrigerating COP varies from - 10. 55% to 1.09% and 3.64% to 12. 73% respectively for leaving heating water of 45 ℃ and 50 ℃ and the heat recovery integrated refrigerating COP reaches 3.38 to 3.69 and 2. 98 to 3.15 in nominal cooling condition. The refrigerating COP decreases 2. 44% to 4.68% when the temperature rises from 45 ℃ to 50 ℃ with single and double fans. In nominal heating condition, the heating COP decreases 10.96% to 21.58% comparing with no heat recovery situation and the heating COP increases 4.42% with the temperature rising from 45 ℃ to 50 ℃. The integrated heating COP reaches 3.28 and 3.09.
出处 《科学技术与工程》 北大核心 2014年第32期290-296,共7页 Science Technology and Engineering
关键词 部分热回收 风冷热泵 名义工况 运行参数 性能系数 partial heat-recovery air-cooled heat pump nominal working condition operation parameter COP
  • 相关文献

参考文献5

二级参考文献28

  • 1陈超,欧阳军,王秀丽,刘铭.空气源热泵机组冬季除霜热量补偿新方法[J].制冷学报,2006,27(4):37-40. 被引量:11
  • 2季杰 等.家用空调和热水器一体化装置[P].00 2 40603.9.2001-07-06.
  • 3高田秋一.热泵技术的最新发展和进步[A]..第八届全国制冷和热泵学术会议[C].,1997.18~20.
  • 4邹才福.中央空调废热回收利用在酒店使用情况分析[A]..2001年全国热泵和空调技术交流会论文集[C].,2001.152~154.
  • 5DA雷伊andD BA麦克米查尔著.热泵设计和应用-工厂经理、工程师、建筑师和设计师的应用手册[M].北京:国防工业出版社,1985.41-42.
  • 6Reay D A Macmlchel D B A.热泵设计和应用.新能源,1983,(1):3-7.
  • 7范存养.热泵空调及各种热回收系统和空调节能技术[M].同济大学科学技术情报站,1980..
  • 8马最良 唐金泉.人工冰场制冷系统冷凝废热利用的可行性分析.制冷学报,1987,(3):22-26.
  • 9HL von 库伯,F斯泰姆著.王子介译.热泵的理论与实践[M].北京:机械工业出版社,第一版,1986.
  • 10H基思,A哈登费尔特著,耿惠彬译.热泵第一卷导论和基础[M].北京:机械工业出版社,1987.

共引文献77

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部