桂林网区感性无功补偿配置方案探讨 被引量:1

Discussion on Configuration Scheme of Inductive Reactive Power Compensation in Guilin Regional Power Grid
下载PDF
导出
摘要 解决桂林网区220 kV母线电压普遍偏高的问题。通过分析及计算可知,桂林网区220 kV母线电压普遍偏高的主要原因为500 kV变电站及电源运行电压偏高;220kV系统充电无功功率过大;地方小水电、风电等无功功率大量上网。利用500kV变电站现有的低压电抗器,及在无功电压综合灵敏度较高的220kV变电站投入感性无功补偿装置,可有效限制220 kV变电站母线电压水平。感性无功补偿装置采用固定式与动态式补偿相结合的型式,可提高桂林网区电压调节能力。 The problem of general higher 220 kV bus voltage in Guilin regional power grid is solved. By analysis and calculation, it is found that main reasons of general higher 220 kV bus voltage are the higher operation voltage of 500 kV substations and electric power sources, the larger charging reactive power of 220 kV system and the larger reactive power sent up from local small hydro powers and wind powers. The bus voltage level of 220 kV substation can be effectively limited by using available low voltage reactors in 500 kV substation and putting inductive reactive power compensation devices into operation in 220 kV substations which have higher reactive power and voltage comprehensive sensitivity. Inductive reactive power compensation devices, which use the combination type of fixed and dynamic compensation, can improve the voltage regulation capability in Guilin regional power grid.
作者 徐海涛 肖宏
出处 《广西电力》 2014年第5期31-34,共4页 Guangxi Electric Power
关键词 220 kV母线电压 无功功率 感性无功补偿 运行方式 220 kV bus voltage reactive power inductive reactive power compensation operation mode
  • 相关文献

参考文献4

  • 1桂林供电局.桂林市“十二五”配电网规划项目库优化[Z].桂林:桂林供电局,2012.
  • 2桂林供电局.综合考虑分布式可再生清洁电源波动特性的桂林电网无功规划优化[Z].桂林:桂林供电局,2013.
  • 3Q/CSG 20004-2005,电力系统电压质量和无功电力管理标准[S].
  • 4GB 12325-2004,电能质量供电电压允许偏差[S].

同被引文献3

引证文献1

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部